Thermo Pride OPA Installation And Service Manual page 37

Outdoor combination oil-fired furnace and air conditioning unit
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
ii.
iii.
iv.
NOTICE: To achieve proper combustion and the efficiencies
listed in sales brochures, instruments must be used to secure
CO
or O
readings.
2
2
CARBON DIOXIDE (CO
from flue passageway. It is possible to achieve readings of up to
14% CO
(or 2% O
2
2
higher O
) reading with zero smoke measured. To achieve a lower
2
CO
reading, open the air band, or shutter, on the burner until zero
2
smoke is measured.
For example, if a 13% CO
smoke, open the air shutter until zero smoke is measured with a
12% CO
(or 4.5% O
2
Adjustment of the burner to achieve a slightly lower CO
recommended, although it slightly reduces combustion efficiency, to
keep the heating system within normal operating conditions though
external conditions may vary. Some "out-of-spec" conditions which
may adversely affect burner performance are, low oil supply
temperature, dirty (contaminated) oil, low heating content (BTU/gal)
oil, cold heat exchanger surfaces, and downdraft conditions. By
adjusting the burner in this manner, an operational tolerance is
established allowing the burner to function well, even under less
than ideal conditions. This results in less service and maintenance
during a heating season.
FLUE GAS TEMPERATURE: The flue gas temperature will vary to
some extent depending on the heat input rate, duct design, and the
amount of air flow across the heat exchanger. The suggested
minimum net flue gas temperature is 350
gross flue gas temperature is 550
temperature, the higher the heating efficiency. However, stack
temperatures under 350
vapor in the flue gases, which in turn promotes corrosion of the
heat exchanger.
TEMPERATURE RISE: Temperature rise is equal to the supply air
temperature minus return air temperature. Under steady state
operating conditions, the temperature rise across the heating
section should be approximately 65
will slightly lower the heating efficiency. A lower temperature rise
will slightly raise efficiency, but may cause condensation.
) OR OXYGEN (O
2
), but it is better to have a slightly lower CO
(or 3.5% O
2
).
2
0
F may result in condensation of water
0
F. A higher temperature rise
0
36
): Take a CO
2
) is recorded at a trace of
2
reading is
2
F, and the maximum
0
F. The lower the flue gas
sample
2
(or
2