Ferroli PEGASUS F2 N 2S Instructions For Use, Installation And Maintenance page 23

Cast iron gas boiler for heating with electronic ignition and flame control
Hide thumbs Also See for PEGASUS F2 N 2S:
Table of Contents

Advertisement

Pegasus F2 N 2S
Pilot light unit
Key
1
Combustion chamber door
2
Inspection door
3
Pilot burner
4
Ignition electrode
5
Detection electrode
6
Pilot nozzle
7
Gas supply pipe
Cleaning the boiler and fl ue
To clean the boiler properly (Fig. 22):
• Turn off the gas ahead of the unit and disconnect the electrical power supply.
• Take the front panel off the boiler (see Fig. 15).
• Lift the boiler cover by pressing upwards (see also Fig. 3-4).
• Remove the insulation covering the anti-backfl ow device.
• Remove the fume chamber closing plate and the associated
insulation.
• Remove the burner unit (see preceding paragraph).
• Using the brush provided, clean the fume evacuation ducts
between the cast iron elements of the boiler casing, lastly
removing the dirt with a vacuum cleaner.
• Carefully reassemble all the previously disassembled parts and
check the airtightness of the gas circuit and the combustion
ducts.
• During cleaning operations take care not to damage the fume
thermostat bulb mounted on the back of the fume chamber.
Key
1
Screws securing the boiler cover
2
Boiler cover
3
Fume chamber closing plate
4
Fume chamber insulation
5
Brush
6
Combustion analysis plug
5
fi g. 21
fi g. 22
3 ÷ 4 mm
3
7
4
1
2
3
4
6
5
23