5.3
Semi-Annual Checks and Service
Check Burner Manifold Pressure
This task should be performed by qualified service personnel only.
1. Ensure that the gas valve knob is in the OFF position.
2. Remove the pressure tap plug from burner manifold.
(see photo).
3. Insert the fitting for a gas-pressure measuring device
into the pressure tap hole.
The frypot must be filled with shortening or
water during this procedure.
4. Place the gas valve in the PILOT position and light. When the
burner lights and continues to burn, note gas pressure reading
and compare to the accompanying tables.
5. To adjust burner gas pressure, remove the cap from the gas
valve regulator adjustment screw.
6. Increase the setting on the thermostat until the burner comes on.
7. Monitor the gas pressure reading on the man-ometer or
pressure gauge.
8. Adjust the gas valve regulator adjustment screw to obtain the
prescribed pressure. See the Rating Plate. Turning the screw
clockwise increases pressure, counterclockwise decreases
pressure.
35 SERIES GAS FRYERS
CHAPTER 5: PREVENTIVE MAINTENANCE
WARNING
WARNING
A manometer or water column pressure gauge
meter is connected to the manifold here.
Burner Manifold Gas Pressures
Natural Gas Lacq
(G20) under 20 mbar
Natural Gas Groningue *
(G25) under 25 mbar
Natural Gas Groningue
(G20) under 20 mbar
Propane
(G31) under 37 or 50 mbar
* Belgian specifications on 2-6
5-5
Non-CE Standard
Burner Manifold Gas
Pressures
Gas
Pressure
Natural
4.0" W.C.
0.73 kPa
LP
8.25" W.C.
2.05 kPa
CE Standard
Pressure
Gas
(mbar)
9
11
11
22.5