Converting To Another Gas Type - Frymaster 35 Series Installation And Operation Manual

Gas fryer
Hide thumbs Also See for 35 Series:
Table of Contents

Advertisement

4. It is suggested that the burner manifold pressure
be checked at this time by the local gas company
or an authorized service agent. Refer to "Check
Burner Manifold Pressure" in Chapter 5 of this
manual for the proper procedure.
CE Standard MJ35 Burner Manifold Pressure
Gas
Natural Gas Lacq
(G20) under 20 mbar
Natural Gas Groningue
(G25) under 25 mbar
Natural Gas Groningue
(G20) under 20 mbar
Propane
(G31) under 37 or 50 mbar
(1) mbar = 10,2 mm H2O
5. Check the thermostat calibration or temperature programmed into the computer. For units equipped
with thermostat controls, refer to the Thermostat Calibration instructions in Chapter 7.
2.5

Converting to Another Gas Type

Your fryer is configured at the factory for either natural gas or Propane (LP) gas.
If you desire to switch from one type of gas to another, a gas conversion kit must be installed by a
Factory Authorized Service Center technician.
Switching to a different type of gas without installing the proper conversion kit may
NEVER ATTACH YOUR FRYER TO A GAS SUPPLY FOR WHICH IT IS NOT
35 SERIES GAS FRYERS
CHAPTER 2: INSTALLATION INSTRUCTIONS
Pressure
Burners
Consumption
(mbar)
3
9
2.8m
/h
3
11
3,00m
/h
3
11
3,00m
/h
22.5
2,05 kg/h
result in fire or explosion!
CONFIGURED!
Non-CE Standard Burner Manifold Gas Pressure
Gas
Natural
LP
CE Standard MJ35 (Belgium) Burner Manifold Pressure
Gas
Natural Gas Lacq
(G20) under 20 mbar
Natural Gas Groningue
(G25) under 25 mbar
Natural Gas Groningue
(G20) under 20 mbar
Propane
(G31) under 37 or 50 mbar
DANGER
2-6
Pressure
4" WC
0.87 kPa
9" WC
2.24 kPa
Pressure
Burners
Consumption
(mbar)
3
9
2.8m
/h
3
9
2.8m
/h
3
9
2.8m
/h
22.5
2,05 kg/h