10. CONNECTING TO HONEYWELL GENUS NETWORK

10.1. Icon Controller Identification on Genus
Icon has to be given a name (alias) in order to log onto the Genus
following naming convention is required for Genus network identification and
defrost capabilities.
The Icon controller name is displayed as 'ICXX-Y' on Genus network. Where 'XX'
is the StUB number and 'Y' is the CASE number.
A stub number 'XX' represents the refrigeration section where the Icon controller
is situated within the supermarket. A case number 'Y' represents the case within
the stub.
1.
Disconnect or ensure that the controller is not logged on the network by
depressing the buttons LIGHT+DOWN for 5 sec: the controller will display
OFFLINE
2.
Connect Genus
controller. OBSERVE POLARITY
3.
Set the StUb parameter between 0..99
4.
Set the CASE parameter between 0...9,A,B,C,D,E,F,G,H,I,L,P,T,U,Y
5.
Enable the controller to communicate on the network by depressing the
buttons LIGHT+UP for 5 sec: the controller will display ONLINE
1.
To log off from the Genus network depress the buttons LIGHT+DOWN for
5 seconds, the controller will display OFFLINE
24
ICON 343C / 363C USER GUIDE

10.2. Network Logging-On Procedure

®
®
network cable to Genus

10.3. Network Logging-Off Procedure

Network
®
®
network. The
socket at rear end of the Icon
EN2B-0004UK07 R0304