SPECIFICATIONS
Operating Voltage Range:
Operating Current @ 24 VDC:
Maximum Alarm Current:
Maximum Current:
Operating Humidity Range:
Installation Temperature:
Fixed Temperature Rating:
High Heat Temperature Rating:
Rate-of Rise Detection:
Height:
Diameter:
Weight:
UL 521 listed for Heat Detectors
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
Before installing sensors, please read the system wiring and installation man-
ual thoroughly. This manual provides detailed information on sensor spac-
ing, placement, zoning, and special applications. Copies of these manuals are
available from Honeywell.
GENERAL DESCRIPTION
Models IDP-HEAT-W, IDP-HEAT-IV, IDP-HEAT-ROR-W, and IDP-HEAT-ROR-IV,
IDP-HEAT-HT-W, and IDP-HEAT-HT-IV are field programmable intelligent sen-
sors that utilize a state-of-the-art thermistor sensing circuit for fast response.
These sensors are designed to provide open area protection with 50-foot spac-
ing capability as approved by UL 521. The intelligent temperature sensor can
be programmed as either a 135°F fixed temperature sensor, a rate of rise and
135°F fixed temperature sensor or a 190°F high temperature sensor through
the Fire Alarm Control Panel (FACP).
Two LEDs on each sensor light to provide a local, visible sensor indication.
Remote LED annunciator capability is available as an optional accessory
(Part No. RA100Z). Rotary dial switches are provided for setting the sensor's
address. (See Figure 1.)
FIGURE 1: ROTARY ADDRESS SWITCHES
7
8
6
9
5
10
11
4
12
3
13
2
14
1 0
15
TENS
Honeywell Farenhyt panels offer different feature sets across different models.
As a result, certain features of the Intelligent Programmable Temperature Sen-
sors may be available on some control panels, but not on others. These de-
vices support IDP protocol mode. The possible features available if supported
by the control panel are:
1.
The sensor's LEDs can operate in three ways—on, off, and blinking–and
they can be set to red, green, or amber. This is controlled by the panel.
2.
The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs. Please refer to the operation manual for
the UL listed control unit for specific operation of these models
15 to 32 Volts DC Peak
200 uA (one communication every 5 seconds with green LED blink on communication)
2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
10% to 93% Relative Humidity, Non-condensing
Set for fixed-temperature or rate-of-rise (ROR): –4°F to 100°F (–20°C to 38°C)
Set for high-heat: –4°F to 150°F (–20°C to 66°C)
135°F (57°C)
190°F (88°C)
Responds to greater than 15°F/minute or 135°F (8.3°C/minute or 57°C)
2.0˝ (51 mm) installed in B300-6 Base
6.2˝ (156 mm) installed in B300-6 Base
3.4 oz. (95 g)
7
8
6
9
5
4
3
2
1 0
ONES
C0162-00
12 Clintonville Road, Northford, CT 06472-1610
3.
Devices are point addressable up to 159 addresses.
4.
The heat sensor operates as a programmable heat detector.
NOTE: In panels where this feature is not available the IDP-HEAT-W and
IDP-HEAT-IV will default to a 135°F fixed heat detector. IDP-HEAT-ROR-W
and IDP-HEAT-ROR-IV will default to a 135°F fixed heat detector and
rate-of-rise. IDP-HEAT-HT-W and IDP-HEAT-HT-IV will default to a 190°F
high temperature heat detector.
Intelligent programmable temperature sensors require compatible addressable
communications to function properly. Connect these sensors to listed-compat-
ible control panels only.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes and the Authority Having Jurisdiction. Proper wire
gauges should be used. The installation wires should be color coded to limit
wiring mistakes and ease system troubleshooting. Improper connections will
prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
1.
Wire the sensor base (supplied separately) as shown in the wiring
diagram. (See Figure 2.)
2.
Set the desired address on the rotary dial switches. (See Figure 1.)
3.
Install the sensor into the sensor base. Push the sensor into the base
while turning it clockwise to secure it in place.
4.
After all sensors have been installed, apply power to the control unit and
activate the communication line.
5.
Test the sensor(s) as described in the TESTING section of this manual.
FIGURE 2. WIRING DIAGRAM:
Remote
Annunciator
+
-
(+)
+
+
2
RA
1
3
(–)
(–)
CLASS A OPTIONAL WIRING
(+)
1
Phone: 203-484-7161 Fax: 203-484-7118
www.Farenhyt.com
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
+
+
+
+
2
2
RA
RA
1
1
3
3
I56-6533-000
11/15/2017
C0129-10

Advertisement

loading

Summary of Contents for Honeywell Farenhyt Series

  • Page 1 ONES C0162-00 supervise connections. Honeywell Farenhyt panels offer different feature sets across different models. As a result, certain features of the Intelligent Programmable Temperature Sen- sors may be available on some control panels, but not on others. These de- vices support IDP protocol mode. The possible features available if supported –...
  • Page 2 – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. Honeywell ® and Farenhyt ® are registered trademarks of Honeywell International, Inc. I56-6533-000 ©2017 Honeywell. 11/15/2017...

This manual is also suitable for:

Idp-heat-wIdp-heat-ivIdp-heat-ror-wIdp-heat-ror-ivIdp-heat-ht-wIdp-heat-ht-iv