Honeywell ICON-343C User Manual page 18

Refrigeration controller
Table of Contents

Advertisement

ICON 343C / 363C USER GUIDE
No
8
9
10
11
12
EN2B-0004UK07 R0304
Parameter Configuration of the Icon 343C / 363C Controller (continued)
Limits/options
Code
[default
values]
0...99 min
ALdy
[10]
dCSt
1...999 h
[4]
1...999 min
dFCt
[30]
-55...+50 °C
dFEt
-67...+122 °F
[10]
0...99 min
dFdL
[10]
Resolution
Low and high temperature alarm delay: this
parameter fixes the time interval in minutes
between the moment in which the conditioned
ambient
SEtP+HtAd (1, 6) and the moment the ALHt
alarm signal is given, provided that during this
time interval, the ambient temperature always
remains above SEtP+HtAd.
1 min
Likewise it fixes the time interval in minutes
between the moment in which the conditioned
ambient temperature drops below the value
SEtP-LtAd (1, 7) and the moment the ALLt alarm
signal is given, provided that during this time
interval, the ambient temperature always remains
below SEtP-LtAd.
Time interval between defrost cycles:
parameter fixes the time interval between the
beginning of a defrost cycle and the beginning of
the next one.
When the defrost cycle is regulated by this
parameter (dCSt), counting of the time interval
between defrost cycles restarts from zero, every
1 h
time a defrost cycle is started manually.
During the defrost cycle the settings in parameter
dIdF (22) are displayed.
Please remember that the value set in this
parameter must be greater than the maximum set
interval between two defrost cycles start times set
in parameters tIN1...tIN6.
Maximum defrost cycle time: this parameter
fixes the maximum defrost cycle time, provided
1 min
the evaporator defrost-end temperature is not
reached, which is set in parameter dFEt (11), or
an evaporator probe failure occurs.
Defrost-end temperature: this parameter fixes
the
evaporator
1/0.1 °C (°F)
reached, ends the defrost cycle. For security
purposes, defrosting ends after the time set in
parameter dFct (10) ends.
Delay of real defrost-end temperature display:
this parameter fixes the tim e interval, that starts
at the end of a defrost cycle (including drain-
down time), and during which the controller
displays the last temperature value shown before
1 min
the current defrost cycle started, provided the real
temperature value of the conditioned ambient is
higher than said value.
If not, and in any case at the end of the above
mentioned time interval, the controller will again
display the real ambient temperature.
17
Description
temperature
exceeds
temperature,
which,
the
value
this
when