ICON-343C / ICON-363C
REFRIGERATION CONTROLLER
USER GUIDE
Copyright © 2004 Honeywell Control Systems Ltd.
All Rights Reserved
EN2B-0004UK07 R0304

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell ICON-343C

  • Page 1 ICON-343C / ICON-363C REFRIGERATION CONTROLLER USER GUIDE Copyright © 2004 Honeywell Control Systems Ltd. All Rights Reserved EN2B-0004UK07 R0304...
  • Page 2 ICON 343C / 363C USER GUIDE Trademark Information Genus® is a registered trademark of Honeywell Control Systems Ltd. EN2B-0004UK07 R0304...
  • Page 3: Table Of Contents

    9. REAL TIME CLOCK AND DEFROST SETUP .......................23 9.1. Setting and Displaying the Real Time Clock....................23 9.2. Setting the Daily Defrost Cycles on the Real Time Clock................23 10. CONNECTING TO HONEYWELL GENUS NETWORK ..................24 ® 10.1. Icon Controller Identification on Genus Network..................24...
  • Page 4: Safety Instructions

    Not complying with the above indications could cause malfunctions and entail unpredictable consequences. This controller is guaranteed by Honeywell to have a specific immunity level, in compliance with CE regulations, against irradiated and conducted electromagnetic disturbances. By irradiated electromagnetic disturbances we recommend to screen the controller with a metal screen connected to ground.
  • Page 5: General Description

    ICON 343C / 363C USER GUIDE 3. GENERAL DESCRIPTION The Honeywell Icon 300 Series is a microprocessor controlled thermostat, powered by AC 230 V, 50/60 Hz, and operates with up to three NTC or PT1000 probes (air-on, air-off and evaporator probes), and has up to six relay outputs (alarm, auxiliary, light, compressor, defrost and fan), and two digital inputs (doorswitch and auxiliary).
  • Page 6: Technical Specifications

    Storage temperature - 20…+ 80 °C / - 4…176 °F Table 1. Technical Specifications Honeywell reserves all rights to modify the technical features of its instruments as well as to discontinue the production of any model without previous notification. EN2B-0004UK07 R0304...
  • Page 7: Installation

    6.2. Probes We recommend the use of probes such as Honeywell 2k ohm NTC thermistor temperature probes (Part Number: TP002K). Both the air-on and air-off probe is to be installed inside the coldroom or refrigerated display case where it is protected from direct air flow (i.e., far from...
  • Page 8 ICON 343C / 363C USER GUIDE Fig. 1. – Electrical wiring diagram of the ICON 343C controller 6,7: light output comms contact input 8,9: controller power supply not used 10,11: compressor output door contact input 12,13: defrost output 21,22: air-off probe input 14,15: fan output 23,24:...
  • Page 9: Fitting

    ICON 343C / 363C USER GUIDE 6.4. Fitting When fitting the controller, leave enough room at the rear to avoid compressing or excessively bending the cables. The overall instrument dimensions and panel cut out are given in Figure 3. below. SCREW FIXTURE Note: In order to access the screw fixture (x2) please remove the front...
  • Page 10: Probe Self Detect

    ICON 343C / 363C USER GUIDE 6.5. Probe Self Detect The Icon 300 series has a feature that allows only the AIR-OFF probe to be fitted. If this function is used then the controller will not alarm on any probes that are missing. Again, this applies to the AIR OFF probe if this is the only probe that is fitted, and therefore the weighting parameter pair must be set to 0%.
  • Page 11: Icon Front Panel

    ICON 343C / 363C USER GUIDE 7. ICON FRONT PANEL 7.1. Functions of the Front Panel The front panel of the ICON 343C / 363C controller is shown in Fig. 4. The front panel includes a four-digit display and four decimal points, a keyboard with eight keys , and has one red and four green LED alerts.
  • Page 12: Controller Front Panel Keys

    ICON 343C / 363C USER GUIDE 7.3. Controller Front Panel Keys References Symbols Description To Fig. 4. REAL TIME CLOCK LOW HUMIDITY DOWN LIGHT DEFROSTING ON/OFF Table 3. Controller Keys 7.4. Functions of the Keys The function of the individual keys and combinations thereof are listed below. Please note that the use of the keys in a combined manner is only possible on the controller front panel.
  • Page 13 ICON 343C / 363C USER GUIDE UP KEY • When depressed while selecting the main set point or parameter settings, increases the numerical value shown on the display. DOWN KEY • When depressed while selecting the main set point or parameter settings, decreases the numerical value shown on the display.
  • Page 14 UP and LIGHT KEYS • When depressed simultaneously for 5 seconds, allows the controller to ® log onto the Honeywell Genus network and communicate. DOWN and LIGHT KEYS • When depressed simultaneously for 5 seconds, allows the controller to ®...
  • Page 15: Led Functions

    ICON 343C / 363C USER GUIDE 7.5. LED Functions ALARM LED • When switched on, this indicates the presence of an alarm situation. The alarm situations are accompanied by an intermittent bleeping sound and are shown with a message on the display. LOW HUMIDITY LED •...
  • Page 16: Configuration Parameters

    ICON 343C / 363C USER GUIDE 8. CONFIGURATION PARAMETERS The configuration parameters, their description, and their respective limits or options as well as their default values are given in Table 4 (page 17). When the controller is in the normal operating mode it is possible to change parameter configuration by proceeding the following way: •...
  • Page 17: Parameter Configuration Of The Icon 343C & 363C Controller

    ICON 343C / 363C USER GUIDE 8.1. Parameter Configuration of the Icon 343C & 363C Controller Limits/options Code Resolution Description [default values] Main set point: when the compressor is switched on to reduce the conditioned ambient LSPL…HSPL temperature, this parameter sets SEtP 1/0.1 °C (°F)
  • Page 18 ICON 343C / 363C USER GUIDE Parameter Configuration of the Icon 343C / 363C Controller (continued) Limits/options Code [default Resolution Description values] Low and high temperature alarm delay: this parameter fixes the time interval in minutes between the moment in which the conditioned ambient temperature exceeds...
  • Page 19 ICON 343C / 363C USER GUIDE Parameter Configuration of the Icon 343C / 363C Controller (continued) Limits/options Code Resolution Description [default values] Air-off probe offset: this parameter fixes the positive or negative correction -20…+20 °C (°F) OFP1 1/0.1 °C (°F) to be made of the value measured by air-off probe...
  • Page 20 ICON 343C / 363C USER GUIDE Parameter Configuration of the Icon 343C / 363C Controller (continued) Limits/options Code Resolution Description [default values] Fan start delay at controller startup and after defrost cycle: this parameter fixes the time interval that starts at controller start-up or at the end of a defrost cycle...
  • Page 21 ICON 343C / 363C USER GUIDE Parameter Configuration of the Icon 343C / 363C Controller (continued) Limits/options Code Resolution Description [default values] Compressor operating mode during the defrost cycle: this parameter determines OFF, On the compressor function mode during a CodF [OFF] defrost cycle, i.e., always switched off when...
  • Page 22 ICON 343C / 363C USER GUIDE Parameter Configuration of the Icon 343C / 363C Controller (continued) Limits/options Code Resolution Description [default values] Compressor on-time during probe failure: this parameter fixes the time interval that alternates with the time set in 1...99 min COOn 1 min...
  • Page 23 ICON 343C / 363C USER GUIDE Parameter Configuration of the Icon 343C / 363C Controller (continued) Limits/options Code Resolution Description [default values] tIN1 ,…,6 defrost cycle starting times: in this parameter up to six defrost tIN2 cycle starting times can be set, or the tIN3 same can be disabled (option - - - - ).
  • Page 24: Real Time Clock And Defrost Setup

    3. Press SET to confirm new value. 9.2. Setting the Daily Defrost Cycles on the Real Time Clock It is possible to set-up 6 defrost cycles per day on Icon models: ICON-343C & ICON-363C. The time parameters regarding this function are: tIN1, tIN2, tIN3, tIN4, tIN5 & tIN6...
  • Page 25: Connecting To Honeywell Genus Network

    ICON 343C / 363C USER GUIDE 10. CONNECTING TO HONEYWELL GENUS NETWORK 10.1. Icon Controller Identification on Genus Network ® ® Icon has to be given a name (alias) in order to log onto the Genus network. The following naming convention is required for Genus network identification and defrost capabilities.
  • Page 26: Programmable Hotkey

    “-rST” and “OFF”. ® 7. If the Icon is connected to the Honeywell Genus network, manually re-configure controller parameters StUb and CASE to reflect new address. Also manually re- configure DFst (see note below).
  • Page 27: Troubleshooting

    ICON 343C / 363C USER GUIDE 12. TROUBLESHOOTING The ICON controller is able to recognize and to signal seven types of alarm situation. Each alarm type has a corresponding alarm message and actions that are made by the controller (see Table 5). The alarm messages are displayed and alternate with the current displayed value;...
  • Page 28: Warning Messages

    The user can directly request new operating instructions from Honeywell, should those supplied have been damaged or lost. Honeywell reserves the right to modify product features and/or to up-date the operating instructions at any time, without giving prior notice and without the obligation to up-date previously issued versions.
  • Page 29: Notes

    ICON 343C / 363C USER GUIDE 15. NOTES EN2B-0004UK07 R0304...
  • Page 30 ICON 343C / 363C USER GUIDE EN2B-0004UK07 R0304...
  • Page 31 ICON 343C / 363C USER GUIDE EN2B-0004UK07 R0304...