ICON 343C / 363C USER GUIDE
No.
19
20
EN2B-0004UK07 R0304
Parameter Configuration of the Icon 343C / 363C Controller (continued)
Limits/options
Code
[default values]
0...99 min
FAnd
[2]
Con, CoF, OnOn
FAnO
OnOF
[OnOn]
Resolution
Fan start delay at controller startup
and after defrost cycle: this parameter
fixes the time interval that starts at
controller start-up or at the end of a
defrost
cycle
time), during which the fan must remain
switched off in order to not introduce
warm and humid air into the conditioned
ambient air.
At the end of said time interval, the fan
1
will be switched on either immediately, if
the evaporator probe is defective, or
when the evaporator temperature drops
and reaches the value set in parameter
18 (Fant).
The Fand parameter is de-activated
while the controller operates in the low
humidity mode. The fan is always
switched on, except during defrosting
(see parameter 20, FanO).
Fan operating mode:
fixes the type of fan operating mode.
If the Con option is selected, then the
fan operating mode is linked to that of
the compressor, provided the system is
not operating in the low humidity mode.
The fan is always switched on when the
system is operating in the low humidity
mode.
If the CoF option is selected, then the
fan operating mode is linked to that of
the compressor, provided the system is
not operating in the low humidity mode.
The fan is always switched on, except
during the defrost cycle, when the
system is operating in the low humidity
mode.
If the OnOn option is selected, then the
fan is always switched on, except during
the defrost cycle and thereafter for the
time set in parameter 19 (Fand), until the
temperature has reached the value set
in parameter 18 (Fant), provided the
system is not operating in the low
humidity mode. The fan is always
switched
operating in the low humidity mode.
If the OnOF option is selected, then the
fan is always switched on, except during
the defrost cycle and thereafter for the
time set in parameter 19 (Fand). Until
the temperature has reached the value
set in parameter 18 (Fant), provided the
system is not operating in the low
humidity mode. The fan is always
switched on, except during the defrost
cycle, when the system is operating in
the low humidity mode.