Gas Information; Gas Pressure Requirements; Gas Connection - Heat & Glo 350TRSI-AUF Owner's Manual

Hide thumbs Also See for 350TRSI-AUF:
Table of Contents

Advertisement

11

Gas Information

A. Gas Pressure Requirements
WARNING! Risk of Explosion! An in-line regulator
MUST be installed if the gas pressure exceeds 3.7 kPa.
Failure to install a regulator could damage valve.
Pressure requirements for 350TRSI-AUF and 350TRSILP-
AUF fireplaces are shown in the table below.
Two taps are provided on the right hand side of the gas
control for a test gauge connection to measure the inlet
and outlet pressures.
The fireplace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 6 kPa.
If the fireplace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must
be of the handle-less type.
WARNING
Fire Risk
Explosion Risk
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 6 kPa.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 6 kPa.
B. Gas Connection
Note: Have the gas supply line installed in accordance with
local building codes by a qualified installer approved and/or
licensed as required by the locality.
Note: Before the first firing of the appliance, the gas supply
line should be purged of any trapped air.
Note: Consult local building regulations to properly size the
gas supply line leading to the (Rp 1/2 in.) hook-up at the unit.
Inlet Gas Pressure
Outlet (Manifold) Gas Pressure
Maximum Gas Consumption
Burner Injector
Pilot Injector
An in-line regulator MUST be installed if the gas pressure exceeds 3.40 kPa. Failure to install a regulator could damage
valve.
52
Natural Gas
1.13 - 3.40 kPa
.80- .95 kPa
DMS 44 (2.18 mm)
Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. o • 6/12
Incoming gas line should be piped into the valve compart-
ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)
threaded gas inlet connection on the manual shutoff valve.
Leak test all gas line points and the gas control valve prior
to and after starting the gas appliance.
IMPORTANT NOTICE:
ALL Heat & Glo gas appliances)
1. 1/2 in. GAS LINE: Run through cavity 70 mm
above finished hearth level, NOT RIGID, NOT
CLIPPED, with minimum 500 mm into cavity and
120 mm back from plaster face.
2. PVC (COMPOSITE) GASLINE must terminate
minimum 500 mm short of gas heater. Copper pipe
MUST be the final connection to the gas heater.
3. ISOLATING SWITCH: Location within 1 metre
of fireplace, subject to mantelpiece etc. Check to
ensure it remains clear of any mantelpiece instal-
lation.
Leak test all gas line points and the gas control valve prior
to and after starting the gas appliance.
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fittings and connections.
• Do not use open flame.
• After the gas line installation is complete, all
connections must be tightened and checked
for leaks with a commercially-available, non-
corrosive leak check solution. Be sure to rinse
off all leak check solution following testing.
Fittings and connections may have loosened
during shipping and handling.
21 MJ/h
.0181
(Items 1, 2 and 3 applies to
WARNING
Propane
2.75 - 3.40 kPa
2.36 - 2.61 kPa
19.8 MJ/h
DMS 55 (1.32 mm)
.0121