Rinnai E75CN Installation & Servicing Instructions Manual page 73

High effi ciency condensing gas boiler
Table of Contents

Advertisement

Available languages

Available languages

i
NOTICE
15.2 Blocks
Code
Description
External safety contact open
Maximum average T of supply and
return sensor for central heating is
repeatedly exceeded. Operation is
normally possible for the hot water
supply during the block. The pump
continues to operate at minimum
capacity during the block.
Maximum average T of supply
and return sensor for hot water is
repeatedly exceeded. Operation
is normally possible for the central
heating installation during the block.
The pump continues to operate at
minimum capacity during the block.
Incorrect parameter setting for the
minimum or maximum power
A temperature difference has been
detected between the supply and
return sensor whilst the burner is
not in operation. After the average
T has disappeared, the block will
disappear.
fl ue sensor temperature too high
fl ue sensor or thermostat contact
open
fl ue sensor or thermostat contact
closed
fl ue gas thermostat contact open
no water fl ow can be detected
through the controller. De-aeration
cycle is started. When water fl ow
is detected during this cycle, the
de-aeration cycle is terminated
and the burner is released.
The controller checks the water
pressure during static and
dynamic situation.
The frequence of the power supply
deviates more than + or -1.5Hz
The following pages describes more detailed follow up instructions for solving
blockings, errors and practical circumstances. These instructions are only for
by Rinnai trained installers and technicians.
An error, which has been detected, is indicated on the display by a block message.
Blocks can be temporary in nature. The controller will do everything possible to prevent
a system lock and temporarily switching off the boiler as a result of a block. Please
see below for a summary of blocks.
Blocks
with a fi gure on the last 2 characters.
Solution
Rectify error as a result of which by determining contact is open.
Or repair interconnection between 24/25
Check fl ow through the installation.
See the installation instructions for the hydraulic connections to the boiler
(3-Way-Thermostatic valve, Plumbing Kit installed?)
Possible causes: (radiator) shut-off valves closed or blocked water fi lter
Activeted room sensor (RS101) in non leading room (closed thermostatic
radiator valves?) Check pump height.
Check minimum and maximum Temperature difference in Parameter Step
46 + 47.
Check fl ow through the boiler and DHW tank
See the installation instructions for the hydraulic connections to the boiler
Possible causes: (radiator) shut-off valves closed or blocked water fi lter
resistance (coil) in tank to high (see pump height)
Check 3-way-valve on function and pollution.
Call Rinnai
Check the supply and return sensor for the resistance value and replace
the defective sensor
Check the installation for any external heat source and rectify this
Check vent system
Call Rinnai
Call Rinnai
Check vent system
or check parameter 84 for default
- check the installation for the presence of air;If there is a secondary
pump installed and it is not hydraulicly separated, it could cause
pressure differences.
- check the use of balancing valves
check if the pump is functioning and/or that the water pressure sensor is
working properly;
Polluted pump;
Polluted water pressure sensor;
Polluted water fi lter;
Wiring of pump.
check the main power supply
73

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

E110cnE75cpE110cp

Table of Contents