IBM System x3650 M4 Type 7915 Problem Determination And Service Manual page 68

Hide thumbs Also See for System x3650 M4 Type 7915:
Table of Contents

Advertisement

Table 6. IMM2 error messages (continued)
v Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v If an action step is preceded by "(Trained technician only)," that step must be performed only by a trained
technician.
80010701-1406xxxx Sensor DIMM GH VR
Temp going high
(upper non-critical)
has asserted.
80010901-1406xxxx Sensor DIMM GH VR
Temp going high
(upper critical) has
asserted.
80010b01-1406xxxx Sensor DIMM GH VR
Temp going high
(upper
non-recoverable) has
asserted.
80010701-2d01xxxx Numeric sensor PCH
Temp going high
(upper non-critical)
has asserted.
80010901-2d01xxxx Numeric sensor PCH
Temp going high
(upper critical) has
asserted.
80010b01-2d01xxxx Numeric sensor PCH
Temp going high
(upper
non-recoverable) has
asserted.
81010701-2d01xxxx Numeric sensor PCH
Temp going high
(upper non-critical)
has deasserted.
81010901-2d01xxxx Numeric sensor PCH
Temp going high
(upper critical) has
deasserted.
81010b01-2d01xxxx Numeric sensor PCH
Temp going high
(upper
non-recoverable) has
deasserted.
50
IBM System x3650 M4 Type 7915: Problem Determination and Service Guide
Warning
An upper
non-critical sensor
going high has
asserted.
Error
An upper critical
sensor going high
has asserted.
Error
An upper
non-recoverable
sensor going high
has asserted.
Warning
An upper
non-critical sensor
going high has
asserted.
Error
An upper critical
sensor going high
has asserted.
Error
An upper
non-recoverable
sensor going high
has asserted.
Info
An upper
non-critical sensor
going high has
deasserted.
Info
An upper critical
sensor going high
has deasserted.
Info
An upper
non-recoverable
sensor going high
has deasserted.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air from
exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air from
exiting the server.
No action; information only.
No action; information only.
No action; information only.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents