To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL
TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.
CAUTION: D
O NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW
THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY
1. Place the COOL-OFF-HEAT
switch into the COOL position.
2. Press the
button until the temperature
setting is at least 3 degrees below the room temperature. The air
conditioning system should turn on within a few seconds.
NOTE: W
C
HILE IN THE
OOL MODE ONCE THE THERMOSTAT TURNS THE SYSTEM OFF
5
. T
FROM TURNING ON FOR ABOUT
MINUTES
HIS PROTECTS THE COMPRESSOR
. T
5-
IS NECESSARY
O OVERRIDE THE
MINUTE DELAY FOR INSTALLATION
.
PROGRAMMING
3. Put the COOL-OFF-HEAT switch into
the OFF position. The air conditioning
system should turn off. The fan may
continue to run for a short period of time.
4. Put the COOL-OFF-HEAT switch
into the HEAT position.
5. Press the
button until the temperature setting is at least
3 degrees above room temperature. The heating system should turn
on. The fan may not turn on immediately, depending upon the fan
delay built into the furnace.
6. Put the COOL-OFF-HEAT switch
into the OFF position. The heating
system should turn off. Once again,
the fan may have a delay.
7. Put the
AUTO-ON switch
to the ON position. The blower
fan should turn on.
8. Put the
AUTO-ON switch
to the AUTO position. The blower
fan should turn off.

LED Indicator

The LED indicator illuminates during a call for second stage heating or
cooling. The auxiliary stages are used to maintain comfort during
extremes in weather conditions. If the LED is illuminated too frequently
during periods of moderate temperature, check the differential settings
(page 5).
Page 9
50°F (10°C). T
HIS CAN DAMAGE
.
COOL-OFF-HEAT
,
-
A BUILT
IN DELAY KEEPS THE COMPRESSOR
. N
(
O ADDITIONAL TIME DELAY RELAY
DELAY ON BREAK
,
RESET. T
PRESS
HIS WILL ERASE THE DELAY AS WELL AS ALL
COOL-OFF-HEAT
COOL-OFF-HEAT
COOL-OFF-HEAT
AUTO - ON
AUTO - ON
9
)