To Test Thermostat - Robertshaw 8625 User Manual

Digital programmable thermostat 5 - 2 day programmable 2 heat / 2 cool
Hide thumbs Also See for 8625:
Table of Contents

Advertisement

110-1101
7/22/04
8:16 AM

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS
VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL
DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.
CAUTION: DO NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE
IS BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR
CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY.
1. Place the EMER-HEAT-OFF-COOL switch into
the COOL position. The
2. Press the
button until the temperature
setting is at least 3 degrees below the room
temperature. The air conditioning system should turn on within a
few seconds.
NOTE: ONCE THE THERMOSTAT TURNS OFF WHEN IN THE COOL MODE,
A BUILT IN 5-MINUTE DELAY PREVENTS THE SYSTEM FROM
TURNING ON AGAIN. THIS PROTECTS THE COMPRESSOR. NO
ADDITIONAL TIME DELAY RELAY IS REQUIRED. TO OVERRIDE THE
5-MINUTE DELAY FOR INSTALLATION, PRESS THE RESET BUTTON.
3. Put the EMER-HEAT-OFF-COOL switch into the
OFF position. The air conditioning system
should turn off.
4. Put the EMER-HEAT-OFF-COOL switch into the
HEAT position. The
5. Press the
button until the temperature
setting is at least 3 degrees above room
temperature. The heating system should turn on. The fan may
not turn on immediately, depending on the fan delay built into
the furnace.
NOTE: If HP is selected, the heat will not come on until the 5 minute
short cycle protection has expired.
6. Put the EMER-HEAT-OFF-COOL switch into the
EMER position. The
7. Press the
button until the temperature
setting is at least 3 degrees above room
temperature. The secondary heating system should turn on.
NOTE: The compressor will not turn when in emergency heat mode.
8. Put the EMER-HEAT-OFF-COOL switch into the
OFF position. The heating system should turn
off. The fan may continue to run for a short
period of time.
9. Put the
AUTO-ON switch into the ON position.
The blower fan should turn on. The display will
show a
.
10. Put the
AUTO-ON switch into the AUTO position.
The blower fan should turn off.
Page 6
will be displayed.
emer heat off cool
emer heat off cool
will be displayed.
emer heat off cool
will be displayed.
emer heat off cool
emer heat off cool
6