Thermostat Specification and Selection Guide (table rows continued on facing page)
Type
Action-
Proportional
T-4002
Single
Direct or
Temperature
Reverse
T-4003
Submaster
Direct--Direct
Readjustment
Reverse--
Reverse
Readjustment
T-4054
Dual
Direct or
Temperature
Reverse
Heating/
Cooling
T-4100
Single
Direct or
Temperature
Reverse
T-4110
Single
Direct or
Temperature
Reverse
T-4506
Dual
Dual Direct or
Temperature
Dual Reverse
Day/Night
with Auto
Switched
Switchover at
Supply
17 PSIG
(119 kPa)
T-4516
Dual
Dual Direct with
Temperature
Auto Switchover
Day/Night
at 17 PSIG
Switched
Supply and
Switchline
T-4600
Dual
Dual Direct,
Temperature
Dual Reverse,
Heating/
or
Cooling
Direct/Reverse
T-4756
Dual
Direct/Reverse
Temperature
Heating/
Cooling
Switched
Supply
4 T-4000 Product Bulletin
Sensitivity
Flow Capacity
Adjustable from .75
400 SCIM
to 4 PSI/F° (9 to
(107 mL/s)
50 kPa/C°)
Factory set at approx.
2.5 PSI/ F°
(32 kPa/C°)
Fixed at approx.
400 SCIM
2.5 PSI/ F°
(107 mL/s)
(32 kPa/C°)
Adjustable from 1 to
400 SCIM
3 PSI/F° (12 to
(107 mL/s)
38 kPa/C°), Factory
set at approx.
2.5 PSI/ F°
(32 kPa/C°)
Adjustable from 1 to
45 SCIM (12 mL/s)
3 PSI/F° (12 to
with .007 in.
38 kPa/C°), Factory
Restrictor,
set at approx.
25 SCIM (7 mL/s)
2.5 PSI/ F°
with .005 in.
(32 kPa/C°)
Restrictor
Adjustable from 1 to
45 SCIM (12 mL/s)
3 PSI/F° (12 to
with .007 in.
38 kPa/C°), Factory
Restrictor,
set at approx.
25 SCIM (7 mL/s)
2.5 PSI/ F°
with .005 in.
(32 kPa/C°)
Restrictor
Adjustable from .75
400 SCIM
to 4 PSI/F° (9 to
(107 mL/s)
50 kPa/C°)
Factory set at approx.
2.5 PSI/ F°
(32 kPa/C°)
Adjustable from .75
400 SCIM
to 4 PSI/F° (9 to
(107 mL/s)
50 kPa/C°)
Factory set at approx.
2.5 PSI/ F°
(32 kPa/C°)
Adjustable from 1 to
45 SCIM (12 mL/s)
3 PSI/F° (12 to
with .007 in.
38 kPa/C°)
Restrictor 25 SCIM
Factory set at approx.
(7 mL/s) with .005 in.
2.5 PSI/ F°
Restrictor (for each
(32 kPa/C°)
output)
Adjustable from .75
400 SCIM
to 4 PSI/F° (9 to
(107 mL/s)
50 kPa/C°)
Factory set at approx.
2.5 PSI/ F°
(32 kPa/C°)
Air
Supply Pressure *
Consumption
20 SCIM
13 to 25 PSIG (91 to
(5 mL/s)
175 kPa)
Nominal 20 PSIG
(140 kPa)
20 SCIM
Supply Pressure:
(5 mL/s)
13 to 25 PSIG (91 to
175 kPa) Nominal
20 PSIG (140 kPa)
Master Pressure:
Variable input 0 to
20 PSIG (0 to 140 kPa)
38 SCIM
13 to 25 PSIG (91 to
(10 mL/s)
175 kPa)
Nominal 20 PSIG
(140 kPa)
45 or 25 SCIM
13 to 25 PSIG (91 to
(12 or 7 mL/s)
175 kPa)
Depending on
Nominal 20 PSIG
Restrictor
(140 kPa) restricted
45 or 25 SCIM
13 to 25 PSIG (91 to
(12 or 7 mL/s)
175 kPa)
depending on
Nominal 20 PSIG
restrictor
(140 kPa) restricted
20 SCIM
13 to 25 PSIG (91 to
(5 mL/s)
175 kPa),
Nominal Day: 15 PSIG
(105 kPa)
Nominal Night: 20 PSIG
(140 kPa)
20 SCIM
Supply Pressure (nominal):
(5 mL/s)
15 PSIG
(105 kPa)
20 PSIG (140 kPa)
Switchline Pressure
(nominal):
0 PSIG (0 kPa)
20 PSIG (140 kPa)
50 or 90 SCIM
13 to 25 PSIG (91 to
(14 or 24 mL/s)
175 kPa)
Depending on
Nominal 20 PSIG
Restrictors
(140 kPa) restricted
20 SCIM
13 to 25 PSIG (91 to
(5 mL/s)
175 kPa)
Nominal 15 PSIG
(105 kPa) Direct, 20 PSIG
(140 kPa) Reverse, or Vice
Versa