Powerboost1 Module Information - Honeywell 800-04433V1 Installation And Setup Manual

Commercial fire communicator
Table of Contents

Advertisement

iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide

PowerBoost1 Module Information

LED Indicator
AC
(green)
ACTIVE
(green)
LOW BATT (yellow)
TROUBLE (yellow)
Notes:
If AC power is lost and the battery voltage falls below 10v, the module's output voltage will be
turned off. The output power is turned back on when AC power is restored.
You must use the DIP switch settings shown below.
STATUS
AC power available.
Cyclical flashing – normal communications.
Repetition of 3 flashes – loss of communications.
Missing or low battery.
One or more trouble conditions exist, such as; overload, output supervision,
ground fault, or charger failure.
PowerBoost 1
LOW BATT LED
INDICATOR
TROUBLE LED
INDICATOR
Confiure DIP switch
ON
as shown:
1
2 3 4
5
ON
(Switch handle = white)
AC LED
INDICATOR
ACTIVE LED
INDICATOR
iPGSM-COM-003-V0
– 9 –
1
2 3 4
5