Application Example: Sliding Waveguide on Anaerobic
Digesters
Notes:
• Only set P837 if the product is at least 2m (78") away from the flange face. If it is
closer, leave P837 at 1 until the level drops and the distance increases beyond
2m (78").
P006
P007
Parameter
P999
P001
P002
P003
P004
P005
P006
P007
P820
P830
P837/838
(Note above)
Run: To start normal operation, press the PROGRAM key
Page 52
Enter
----
master reset
1
mode of measurement
1
material
2
measurement response
240
antenna
1
units
10
empty distance
8
span
8
algorithm
7
TVT type
2 & 1
Auto False Echo Suppression
SITRANS LR 300 – INSTRUCTION MANUAL
The raised position is for installation and
maintenance. The lowered position is for
operation. Program the unit for operation
in the lowered position.
Horn
This application is to obtain a level
measurement and corresponding 4-20 mA
output proportional to the sludge level on
a digester. The bottom of the
SITRANS LR 300 mounting flange is 10m
from the bottom of the digester when the
SITRANS LR 300 is lowered to its normal
operating position.
The empty level is 0m (bottom) and the full
level (span) is 8m from the bottom. The
maximum rate of filling or emptying is
= level
= liquid
= 1m/minute
= factory
= meters
= 10m
= 8m
= bLF (best of Largest or First)
= factory
.
7ML19985CL02