RUN/PROGRAM

When you select PROGRAM mode, the SITRANS LR 300 stops responding to the process.
It stores the most recent measurement, and holds the associated readings and mA signal
output. The unit reverts to the parameter last addressed during the previous program
session.
When you select RUN mode, the transceiver resumes operation. The reading and mA
output default to the last measurement taken. The reading and associated outputs
migrate to the current process level at a rate controlled by the measurement response
(P003).
If the SITRANS LR 300 is left in PROGRAM mode for 10 minutes without input, it
automatically reverts to RUN mode.