Daikin H-Series Engineering Data page 46

H-series cooling only / heat pump split-system room air conditioners
Hide thumbs Also See for H-Series:
Table of Contents

Advertisement

EDUS04-924A
1.
Trial operation and testing.
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
For heat pump
1) In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level of 78°F to 82°F (26°C to 28°C) in
cooling mode and 68°F to 75°F (20°C to 24°C) in heating mode.
• For protection, the unit disables restart operation for 3 minutes after it is turned off.
For cooling only
• Select the lowest programmable temperature.
1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level of 78°F to 82°F (26°C to 28°C).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and
parts are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original
operation mode when the circuit breaker is opened again.
2.
Test items.
Indoor and outdoor units are installed properly on
solid bases.
No refrigerant gas leaks.
Refrigerant gas and liquid pipes and indoor drain
hose extension are thermally insulated.
Draining line is properly installed.
System is properly grounded.
The specified wires are used for inter-unit wiring.
Indoor or outdoor unit's air intake or exhaust has
clear path of air.
Stop valves are opened.
Indoor unit properly receives remote controller
commands.
Room Air Conditioners H-Series
Trial Operation and Testing
Test items
3P235796-1F
Symptom
Fall, vibration, noise
Incomplete cooling/heating function
Water leakage
Water leakage
Electrical leakage
Inoperative or burn damage
Incomplete cooling/heating function
Inoperative
Installation Manual
Check
45