Electric Characteristics - Daikin H-Series Engineering Data

H-series cooling only / heat pump split-system room air conditioners
Hide thumbs Also See for H-Series:
Table of Contents

Advertisement

EDUS04-924A

10. Electric Characteristics

Indoor Unit
Outdoor Unit
RKS30HVJU
FTXS30HVJU
RXS30HVJU
RKS36HVJU
FTXS36HVJU
RXS36HVJU
Symbols:
MCA
: Min. circuit amps (A)
MOP
: Max. overcurrent protection (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
Room Air Conditioners H-Series
Power Supply
Hz - Volts
Voltage Range
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
3D063167
3D071271
COMP
MCA
MOP
RHz
RLA
13.5
19.5
20
66
12.2
84
18.9
19.5
20
90
18.4
Notes:
1. RLA is based on the following conditions.
Indoor temp. : 80°FDB / 67°FWB (26.7°CDB / 19.4°CWB)
Outdoor temp. : 95°FDB (35°CDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
Electric Characteristics
OFM
IFM
W
FLA
W
FLA
0.39
0.27
200
64
0.35
0.24
0.39
0.27
200
64
0.35
0.24
23