Trane HUV Installation Operation & Maintenance page 85

Classroom unit ventilators
Table of Contents

Advertisement

Table E2: Minimum Circuit Ampacity (MCA) for Electric Heat Coils with High Static Motors
Unit Size No of Elem
075
100
3
125
150
200
075
100
4
125
150
200
075
100
6
125
150
200
075
100
7
125
150
200
075
100
9
125
150
200
For Trane controls, add the
following values to determine
TOTAL MCA
Volts
Amps
120
0.94
208
0.55
240
0.48
277
0.41
480
0.41
UV-PRC001-EN
Electrical Data
Minimum Circuit Ampacity
Coil
208V
KW
1ph
5.85
38.74
7.8
50.46
9.75
63.67
11.4
73.58
11.4
74.13
7.8
50.46
10.4
66.09
13.0
83.20
15.2
96.42
15.2
96.97
11.7
NA
15.6
NA
19.5
NA
22.8
NA
22.8
NA
13.65
NA
18.2
NA
22.75
NA
26.6
NA
26.6
NA
17.55
NA
23.4
NA
29.25
NA
34.2
NA
34.2
NA
240V
277V
1ph
1ph
33.58
29.09
43.73
37.89
55.18
47.81
63.77
55.25
64.25
55.67
43.73
37.89
57.28
49.63
72.10
62.47
83.56
72.40
84.04
72.82
64.05
55.49
84.36
73.09
105.96
91.81
123.15
106.70
123.63
107.11
NA
64.29
NA
84.82
NA
106.47
NA
123.84
NA
124.26
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
208V
240V
3ph
3ph
23.91
20.72
30.68
26.59
38.94
33.75
44.67
38.72
45.23
39.20
34.59
29.98
44.93
38.94
56.75
49.18
65.49
56.76
66.04
57.24
44.23
38.33
57.78
50.07
72.81
63.10
84.27
73.04
84.83
73.52
54.67
47.38
71.70
62.14
90.21
78.18
104.61
90.67
105.17
91.14
64.55
55.95
84.87
73.56
106.68
92.46
123.87
107.36
124.43
107.84
*
480V
3ph
10.36
13.30
16.87
19.36
19.60
14.99
19.47
24.59
28.38
28.62
19.17
25.04
31.55
36.52
36.76
23.69
31.07
39.09
45.33
45.57
27.97
36.78
46.23
53.68
53.92
85