Coil Control Valve
Chilled water, hot water and steam coils accommodate control valves when selecting options
8,9,G,H,Q,R,T,U,V,W and Z for DIGITS 16 and 17. The control valves are available as a three-point modu-
lating arrangement. The control valve option includes the following:
Threaded connections on both the 2-way and 3-way configurations;
1/2-and 3/4-inch nominal sizing for both the 2-way and 3-way configurations;
Valve motor leads to include an 18-gauge wire, 6-inches in length, with internal strain relief;
2 1/2-inch clearance above cover required for cover removal
Table 13: Control valve pressure drop
2-Way or 3-Way
2
3
Water Valves
GPM
GPM
1/2" - 1.8 Cv
2.85
6.42
(ft)
(ft)
1/2" - 4.6 Cv
3/4" - 7.3 Cv
UV-PRC001-EN
Piping
Coil Valve Control
4
5
6
7
8
GPM
GPM
GPM
GPM
GPM
11.41
17.82
25.67
34.94
(ft)
(ft)
(ft)
(ft)
2.73
3.93
5.35
6.99
(ft)
(ft)
(ft)
(ft)
2-Way Control Valve (3-Point Modulating)
1/2-inch FNPT; 1.8, 4.6 Cv (Digit 16 = 8,9,W,G and 17 = W,G)
Control
Electrical
Stroke
Ambient
2-Way Control Valve (3-Point Modulating)
3/4-inch FNPT; 7.3 Cv (Digit 16/17 = H)
Control
Electrical
Stroke
Ambient
9
1 0
1 1
1 2
13
GPM
GPM
GPM
GPM
GPM
8.84
10.92
13.21
15.72
18.45
(ft)
(ft)
(ft)
(ft)
(ft)
3.51
4.33
5.25
6.24
7.33
(ft)
(ft)
(ft)
(ft)
(ft)
Actuator
3-Point Modulating
24 VAC, 60 HZ
110 seconds
140 F at 95% relative
humidity
Actuator
3-Point Modulating
24 VAC, 60 HZ
50 seconds
140 F at 95% relative
humidity
14
15
16
17
18
GPM
GPM
GPM
GPM
GPM
21.4
24.56
27.95
(ft)
(ft)
(ft)
8.50
9.75
11.10
12.53
14.04
(ft)
(ft)
(ft)
(ft)
(ft)
Valve Body
Connections
1/2-inch threaded
Static Pressure
400 PSI
Close-off
1.8 Cv = 80 psig
Pressure
4.6 Cv = 45 psig
Temperature
Water 200 F Max.
Valve Body
Connections
3/4-inch threaded
Static Pressure
400 PSI
Close-off
75 psig
Pressure
Temperature
Water 200 F Max.
19
20
GPM
GPM
15.65
17.34
(ft)
(ft)
15