Table P9: 2-pipe coil, HW coil
Unit
Size
Coil
Type
H1
H2
H3
075
H4
H5
H6
H1
H2
H3
100
H4
H5
H6
H1
H2
H3
125
H4
H5
H6
H1
H2
H3
150
H4
H5
H6
H1
H2
H3
200
H4
H5
H6
7 4
Performance Data
H-Coil Heating
Heating (60 EAT, 180 EWT/140 LWT)
TMBH
GPM
41.18
2.06
45.12
2.26
48.74
2.44
53.49
2.67
57.95
2.90
61.84
3.09
52.90
2.65
57.98
2.90
62.65
3.13
71.90
3.59
77.92
3.90
83.19
4.16
66.45
3.32
72.85
3.64
78.73
3.94
90.36
4.52
97.97
4.90
104.61
5.23
99.89
4.99
124.35
6.22
131.66
6.58
108.87
5.44
118.05
5.90
126.08
6.30
120.35
6.02
152.05
7.60
161.68
8.08
132.52
6.63
144.37
7.22
154.87
7.74
WPD
2.85
3.36
3.86
0.70
0.81
0.91
0.97
1.15
1.33
1.41
1.63
1.84
1.67
1.98
2.28
2.45
2.83
3.19
2.70
4.03
4.48
3.88
4.49
5.05
3.80
5.84
6.54
5.52
6.44
7.32