Table P17: K1, K2 coils (continued)
Unit
Size
Coil Type
K1
K1
K1
K1
K1
K1
150
K2
K2
K2
K2
K2
K2
K2
K2
K2
200
K2
K2
K2
Notes:
• Condensate trap for the steam coil option is field installed.
• Static pressure for the K1, K2 options should be modeled after the H1-coil option.
• Steam coils that function at 5 psig or less should not utilize valve control. Valve control may starve the
coil, causing stratification.
8 2
Performance Data
Steam Coils
EAT
TMBH
5 PSIG
-20
166.93
0
153.44
20
139.94
40
126.45
60
112.96
70
106.21
-20
243.70
0
224.72
20
204.96
40
185.20
60
165.43
70
155.55
-20
286.51
0
266.20
20
244.09
40
221.28
60
197.66
70
185.86
TMBH
TMBH
10 PSIG
15 PSIG
174.89
181.68
161.40
168.19
147.90
154.70
134.41
141.20
120.92
127.71
114.17
120.96
256.14
263.74
236.38
246.33
216.62
226.57
196.86
206.80
177.09
187.04
167.21
177.16
306.05
317.93
282.43
294.32
258.82
270.71
235.21
274.09
211.59
223.48
199.79
211.67
UV-PRC001-EN