Fan-Coil Air Flow - Trane UniTrane Fan-Coil Installation Operation & Maintenance

Air terminal devices horizontal, vertical, and low vertical
Table of Contents

Advertisement

UNT-PRC001-EN
General Data
Table GD-3. Fan-Coil Air Flow
Motor
FD
FC
Coil
0.05
2R144
240
02
3R144
230
4R144
200
2R144
320
03
3R144
310
4R144
280
2R144
390
04
3R144
370
4R144
340
2R144
610
06
3R144
610
4R144
560
2R144
800
08
3R144
730
4R144
680
2R144
980
10
3R144
1000
4R144
930
2R144
1110
12
3R144
1080
4R144
1000
Note: This is data is based on horizontal concealed model only, with duct inlet, duct outlet and no filter, dry coil, all voltages except
208 V.
ESP
High Static
0.1
0.2
0.3
330
300
280
330
300
270
300
270
250
410
390
350
400
360
330
370
340
300
450
410
380
550
510
470
510
480
440
760
700
650
890
830
770
820
760
710
1020
960
890
1000
930
870
940
870
810
1260
1180
1090
1400
1310
1210
1300
1220
1130
1430
1330
1240
1520
1420
1330
1430
1340
1240
0.4
250
240
220
320
290
270
340
430
400
590
710
660
820
800
750
1010
1120
1040
1140
1220
1150
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents