Vent Termination Locations - Lennox Hearth Products Winslow PI40 Installation And Operation Manual

Pellet-fired fireplace insert country collection
Table of Contents

Advertisement

Vent Termination Locations

Air Supply Inlet
Vent Terminal
Area Where Terminal Is Not Permitted
(From Eave)
USA - 1' Min.
24"
CANADA - 3' Min.
(610mm)
D
E
M
A =
Refer to vent manufacturer's installation instructions for the re-
quired clearance above grade, veranda, porch, deck, or balcony.
B =
Clearance to window or door that may be opened (min. 12"/30cm
above - 48"/1.2m below and to the side)
C =
Clearance to permanently closed window *(min. 12"/30cm)
D =
Vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of *(min. 24"/60cm) from the centerline
of the terminal (min. 22"/55cm) check with local code.
E =
Clearance to unventilated soffit *(min. 12"/30cm)
F =
Clearance to outside corner *(min. 12"/30cm)
G =
Clearance to inside corner *(min. 12"/30cm)
H =
Not to be installed above a meter/regulator assembly within *(min.
36"/90cm) horizontally from the centerline of the regulator.
J =
Clearance to service regulator vent outlet *(min. 72"/1.8m)
K =
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance *(min. 48"/1.2m)
Figure 9
10
Vertical Terminal
Vertical Terminal
C
H
B
F
J
B
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
G
A
Fixed Closed
B
B
K
A
Able To Open
L =
Clearance to a mechanical air supply inlet *(min. 120"/3.1m)
M = **Clearance above paved sidewalk or a paved driveway located on
public property *(min. 84"/2.1m)
N =
***Clearance under veranda, porch, deck, or balcony (min.
12"/30cm)
Note:
*
Local codes or regulations may require different clearances.
**
A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings.
*** Only permitted if veranda, porch, deck, or balcony is fully open on
a minimum of two sides beneath the floor.
USA - 1' Min.
24"
CANADA - 3' Min.
(610mm)
N
L
B
NOTE: Vent requirements are in
accordance with NFPA 211 and CAN/
CSA-B365-M standards

Advertisement

Table of Contents
loading

Table of Contents