Floor Protection - Quadra-Fire Yosemite YOSEMITE-MBK Installation & Operation Manual

Yosemite series non-catalytic, front/side load, wood heater
Table of Contents

Advertisement

The floor must be non-combustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be
non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible floor is not sufficient.
In USA installations, it is necessary to install a non-combustible floor protector at least 16 inches in front and 8 inches to both
sides of the fuel loading doors. See *exception below.
In Canada, similar floor protection must be provided 18 inches (450mm) in front and 8 inches (200mm) from the sides and rear of
the stove. See *exception below.
*EXCEPTION: Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and
extend 2 inches (51mm) beyond each side.
DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY AND ARE NOT TO SCALE.
10-1/2"
(267mm)
Front Fuel
loading door
16" (406mm) from fuel
loading door
(838mm)
33"
Fuel loading doors
Side
Front
8"
(200mm)
(1130mm)
44-1/2"
7004-187F September 1, 2008
Yosemite Wood Stove

FLOOR PROTECTION

Minimum Hearth Requirements ONLY
See page 6 for stove clearances
SIDE FUEL DOOR LOCKED SHUT
36-3/4
"
(933mm)
Minimum
8"
(200mm)
USA
Minimum
BOTH FUEL DOORS ACCESSIBLE
(200mm)
8"
36-3/4"
(932mm)
Minimum
Minimum 16"
(406mm) from
fuel loading
door
USA
Minimum
200mm (8")
200mm
(8")
450mm (18")
1010mm (39-3/4") Minimum
(8")
200mm
200mm
Fuel loading doors
(8")
Side
Front
(49-3/4")
1264mm
200mm
1187mm
(8")
(46-3/4")
Minimum
CANADA
1187mm
(46-3/4")
Minimum
Minimum 450mm
(18")
from each
fuel loading door
CANADA
Minimum
Page 7