Mobile Home Installation - Quadra-Fire Yosemite YOSEMITE-MBK Installation & Operation Manual

Yosemite series non-catalytic, front/side load, wood heater
Table of Contents

Advertisement

R

MOBILE HOME INSTALLATION

1.
An outside air inlet must be provided for combustion and
must remain clear of leaves, debris, ice and/or snow.
It must be unrestricted while stove is in use to prevent
room air starvation which can cause smoke spillage and
an inability to maintain a fire. Smoke spillage can also
set off smoke alarms.
2.
Stove must be secured to the mobile home structure. Use
1/4" (6.35mm) lag bolts with the appropriate length for your
application, to secure stove through pad and into floor.
3.
Stove must be grounded with #8 solid copper grounding
wire or equivalent and terminated at each end with N.E.C.
approved grounding device.
4.
Stove must be installed with an approved UL103 HT
ventilated chimney connector, UL103 HT chimney, and
terminal cap with spark arrestor. Never use a single wall
connector (stove pipe) in a mobile home installation. Use
only double-wall connector pipe, Dura-Vent DVL, Selkirk
metalbestos DS or Security DL double-wall connector or
any listed double-wall connector pipe.
5.
Refer to page 6 of this manual or the Safety/Serial
Number label on the back of the stove for clearances
to combustibles.
6.
Floor protections requirements on pages 7-8 must be
followed precisely.
7.
In Canada, this appliance must be connected to a 6 inch
(152mm) factory-built chimney conforming to CAN/ULC-
629M, STANDARD FOR FACTORY BUILT CHIMNEYS.
Floor protection referenced on pages 7-8 must be
followed.
8.
Use silicone to create an effective vapor barrier at the
location where the chimney or other component penetrates
to the exterior of the structure.
9.
Follow the chimney and chimney connector manufacturer's
instructions when installing the flue system for use in a
mobile home. SEE NOTES BELOW.
10. Burn wood only. Other types of fuels may generate
poisonous gases (e.g., carbon monoxide).
11
If stove burns poorly while an exhaust blower (i.e.
kitchen range hood) is on in home, increase combustion
air.
NOTE: Offsets from the vertical, not exceeding 45°, are
allowed per Section 905(a) of the Uniform Mechanical
Code (UMC). Offsets greater than 45° are considered
horizontal and are also allowed, providing the horizontal
run does not exceed 75% of the vertical height of the
vent. Construction, clearance and termination must be in
compliance with the UMC Table 9C. This installation must
also complies with NFPA 211.
NOTE: Top sections of chimney must be removable to allow
maximum clearance of 13.5 ft. (411cm) from ground
level for transportation purposes.
Page 16
Yosemite Wood Stove
You must use a Quadra-Fire Outside Air Kit
Part 831-1780 for installation in a mobile home.
Floor
Protector
WARNING! NEVER DRAW COMBUSTION AIR FROM
A WALL, FLOOR OR CEILING CAVITY OR FROM ANY
ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.
CAUTION! THE STRUCTURAL INTEGRITY OF THE
MOBILE HOME FLOOR, WALL AND CEILING/ROOF
MUST BE MAINTAINED. (i.e., DO NOT CUT THROUGH
FLOOR JOIST, WALL STUD, CEILING TRUSS, ETC.)
Storm Collar
Joist Shield &
Firestop
Outside Air Floor Vent
Figure 16A
WARNING! DO NOT INSTALL IN SLEEPING ROOM.
7004-187F September 1, 2008
Spark Arrestor
Cap
Roof Flashing
Listed Chimney
Connector
Outside Air Kit
Connector