Vent Diagrams - Heat & Glo SL-350TRS-D Owner's Manual

Hearth and home technologies fireplace owner's manual
Table of Contents

Advertisement

E. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
1. Top Vent - Horizontal Termination Venting
One Elbow
Note: Use SL-D Series
components only.
Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 5.3).
WARNING
Fire Risk.
• When using SL-HRC-SS and SL-HRC-ZC-SS
termination caps on top vented fi replaces, a one
foot minimum vertical vent section is required
before installing fi rst elbow.
Figure 5.4
Heat & Glo • SL-750TRS-IPI-E, SL-550TRS-IPI-E, SL-350TRS-D, SL-350TRS-IPI • 2120-900 Rev. D • 6/07
WARNING
V Minimum
90º Elbow
1/2 ft.
152 mm
1-1/2 ft.
457 mm
2-1/2 ft.
762 mm
3-1/2 ft.
1.1 m
4-1/2 ft.
1.4 m
H
1
V
+ H
1
H
1
H
Maximum
1
SL-350TRS-D
SL-550, SL-750TRS-E
1-1/2 ft.
457 mm
1 ft.
2 ft.
610 mm
2 ft.
3 ft.
914 mm
3 ft.
5 ft.
1-1/2 m
5 ft.
7 ft.
2.1 m
7 ft.
15 ft.
4.6 m
15 ft.
Maximum= 15 ft. (4.6 m)
Maximum= 40 ft. (12.2 m)
1
305 mm
610 mm
914 mm
1-1/2 m
2.1 m
4.6 m
V
1
15