If the area above the ceiling is NOT an attic, position and
secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.
CEILING
NAILS (4 REQUIRED)
NAILS (3 REQUIRED)
Figure 23. Ceiling Firestop (Ceiling Side)
If the area above the ceiling IS an attic, position and secure
the firestop on top of the previously framed hole.
NOTE: Keep insulation away from the vent pipe at least
1 inch (25mm).
NAILS (3 REQUIRED)
CEILING
CEILING FIRESTOP
Figure 24.
Attic Firestop
26
JOIST
CEILING FIRESTOP
RAFTER
Hearth & Home Technologies • BE-36-C, BE-36-CIPI • 397-981 Rev. R • 2/05
C. Vent Termination
SL-Series Venting Only:
For Horizontal Terminations - To attach and secure the
termination to the last section of horizontal vent:
• Rotate and interlock the ends as described at the begin-
ning of the Installing Vent Components section.
• The termination kit should pass through the wall firestops
from the exterior of the building.
• Adjust the termination cap to its final exterior position on
the building.
For trapezoidal cap termination kits:
• Using screws secure the cap to the exterior wall through
the flanges in the cap.
For DVP Venting Only:
Refer to Cinch Pipe and Termination Cap installation in-
structions.
For All Venting:
WARNING: THE TERMINATION CAP MUST
!
BE POSITIONED SO THAT THE ARROW IS
POINTING UP.
WARNING: VENTING TERMINALS SHALL NOT
!
BE RECESSED INTO A WALL OR SIDING. VENT
TERMINATION CLEARANCES MUST BE FOL-
LOWED TO AVOID FIRE DANGER. SEE VENT TER-
MINATION MINIMUM CLEARANCES DIAGRAM ON
FOLLOWING PAGE.
Figure 25. Trapezoid Termination Cap
7 1/4"
(184mm)