Finishing

A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materi-
als (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.
Combustible Mantels
Note: All
measurements
in inches.
4
3
2-1/2
5
Note: Measurement is taken from top of the opening,
NOT the top of the fi replace.
Figure 13.1 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Combustible Mantel Legs or Wall Projections
TOP VIEW
A
FIREPLACE OPENING
MANTEL LEG OR WALL PROJECTIONS
A
If
minimum is ____, then
2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Inches
A
62
87
Millimeters
1
2
Inches
B
25
51
Millimeters
Figure 13.2 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
50
TO CEILING
18
12
11
10
32
9
8
25
7
19
6
18
5
17
16
15
14
13
12
11
10
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
INTERIOR WALL
B
B
maximum is_____.
113
138
164
189
3
4
5
76
102
127
Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S • 2102-900 Rev. O • 12/08
B. Facing Material
• Metal front faces may be covered with non-combustible
materials only.
• Facing and/or fi nishing materials must not interfere with
air fl ow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or fi nishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the fi nished wall and appliance top
and sides using a 300 ºF minimum sealant. Refer to
Figure 13.3.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
NON-COMBUSTIBLE ZONE (Shaded areas)
41 in.
Figure 13.3 Noncombustible Facing Diagram
39-3/8 in.