Shutdown Procedure - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 75 / 80 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

6.12 Shutdown Procedure

When turning off the UPS, the following shutdown procedure should be used.
1) Move the RUN/STOP key switch of the UPS to STOP. Operation of the inverter halts.
Output power is now provided to the load via the bypass circuit. If a power failure
occurs in the commercial power source while in this state, the UPS will lose power and
power to the load will be interrupted. The battery charging circuit and chopper circuit
will remain active.
DANGER
The LCD display shows the following message when in the Bypass operating mode:
Move the MCCB power switch to Off. Power is removed from the UPS and to any
attached loads. All lamps are off and the LCD display shows the following message so
long as there is sufficient power to display it:
Emergency Power Off activation trips the MCCB and power is removed from the UPS and
to any connected loads (see Section 6.6 "EPO Function"). All LEDs are off and the LCD
display will show the following message:
T O S H I B A
Do not touch the UPS terminals even though the operation switch
has been moved to the STOP position. The UPS may be supplying
power through the bypass circuit.
- BYPASS OPERATION
OUTPUT VOLTAGE=208V
>CURRENT 100/100/100%
DATE (DAY) TIME
- OUTPUT SHUT DOWN -
OUTPUT VOLTAGE= 0V
CURRENT=LOW/LOW/LOW%
- OUTPUT SHUT DOWN -
OUTPUT VOLTAGE= 0V
CURRENT=LOW/LOW/LOW%
47
Note: Actual numerical values may
differ from these examples.

Advertisement

Table of Contents
loading

Table of Contents