6.10 Initial Battery Charge

The battery of the UPS must be charged before it is used for the first time or if the unit has
not been used (AC power source removed) for more than 10 days. Use the following
procedure to recharge the battery of the UPS.
1) Switch on power at the UPS input distribution panel.
2) Move the MCCB1 power switch to On (see Section 4 for location). Note: The
3) With the key switch in the STOP position, the AC IN and the BYP lamp will be
4) Turn the Key Switch to RUN and the UPS performs the Automatic Battery Test
Should the Automatic Battery Test fail and the LOW BATTERY message is
displayed use the following procedure:
1) Turn the key switch to STOP.
2) Allow 24 hours for the batteries to charge and, upon completion, move the
3) Repeat Initial Battery Charge procedure (a failure indicates battery
T O S H I B A
battery charging circuit is now activated. The AC IN lamp will be on. The LCD
display (see Section 6.5 "Front Panel Layout") will display the following
message:
- UPS START UP -
> PLEASE WAIT
on and the LCD display will show the following message:
- BYPASS OPERATION -
OUTPUT VOLTAGE=208V
>CURRENT 100/100/100%
(DATE) DAY (TIME)
(The Automatic Battery Test is performed only when the software is enabled
for this function. The default setting is Disabled).
(Allow 24 hours for the batteries to fully charge).
MCCB switch (see Section 4 for location) to off.
replacement required).