YOKOGAWA EJX Series User Manual page 45

Differential pressure and pressure transmitters
Table of Contents

Advertisement

No.
Parameter name
D
AUX SET 1
Auxiliary setting data 1
D10 LOW CUT
Low cut
D11
LOW CUT MODE
Low cut mode
D15 H/L SWAP
Impulse piping
accessing direction
D16 H2O UNIT SEL
H2O unit select
D20 OUT LIMIT (L)
Low side output limiter
D21 OUT LIMIT (H)
High side output limiter
D22 REV OUTPUT
Output reversal
D25 BURNOUT
CPU error
D26 ERROR OUT
Hardware error
D30 SP UNIT
Static pressure unit
D31 SP A/G SLCT
Gauge/Abs select for
static pressure
D32 ATM. PRESS
Coefficient for given
gauge pressure
D33 SP LRV
Lower limit of static
pressure
D34 SP URV
Upper limit of static
pressure*
D35 SP POINT
Decimal place of static
pressure
D36 SP DAMPING
Damping time constant
of SP
D37 SP SELECT
H/L select for static
pressure
D40 TEMP UNIT
Temperature setting
unit
D50 QUICK RESP
Quick response
D55 WRT PROTECT
Write protect indicator
D56 WRT ENABLE
Write protect release
D57 NEW PASSWORD User set password for
write protect
D58 SOFTWR SEAL
Software seal
D60 SELF CHECK
Self-diagnostics
E
AUX SET 2
Auxiliary setting data 2
E10
T. ZERO CMP
Temperature
compensation mode
E11
TEMP ZERO
Zero shift compensation
E30
BI DIRE MODE
Bidirectional mode
E50
DO SELECT
Contact output select
E51
DO SIG. TYPE
Signal type select
E52
D OUTPUT
Contact output
E60
SELF CHECK
Self-diagnostics
*1:
R/W: R = Read only, W = Read & Write
*2:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user's manual.
Item
R/W
*1
W
0.00 to 20.00%
W
LINEAR or ZERO
W
NORMAL or REVERSE
W
@4degC or @20degC
(68.0F)
W
-2.50 to 110.00%
W
-2.50 to 110.00%
W
NORMAL or REVERSE
R
HIGH or LOW
W
BURNOUT DIR or HOLD
W
See C20
W
GAUGE or ABSOLUTE
W
Unit specified in D30
W
-32000 to 32000 within
measurement range
W
-32000 to 32000 within
2
measurement range
W
0 to 4
W
0.00 to 100.00 sec
W
HIGH or LOW
W
degC, degF, or K
W
OFF or ON (enable 0.00 to
0.50 sec at C30)
R
NO or YES
W
8 alphanumeric characters
W
8 alphanumeric characters
R
BREAK or KEEP
R
See A60
W
OFF or ON
W
-99.999 to 99.999%/degC
W
OFF or ON
W
INHIBIT, PRES, SP, TEMP,
PRES/SP, PRES/TEMP,
SP/TEMP, or PRES/SP/
TEMP
W
OFF WHEN ALARM or ON
WHEN ALARM
R
OFF or ON
R
See A60
<8. Parameter Summary>
Content
Default value
10.00%
LINEAR
NORMAL
@4degC
-2.50%
110%
NORMAL
BURNOUT DIR
MPa
ABSOLUTE
0.10133 MPa
0.0 MPa
1
2.00 sec
HIGH
degC
OFF
NO
None
None
KEEP
OFF
0.000%/degC
OFF
INHIBIT
ON WHEN ALARM
OFF
43