YOKOGAWA EJX Series User Manual page 44

Differential pressure and pressure transmitters
Table of Contents

Advertisement

 BRAIN Communication Parameter List
Instruments to which applicable:
F: Differential pressure transmitters
P: Absolute and gauge pressure transmitters
L: Flange mounted differential pressure transmitters
No.
Parameter name
01
MODEL
Model
02
TAG No.
Tag number
03
SELF CHECK
Self-diagnostics
A
DISPLAY
Measured data display
A10
OUTPUT
Output (in %)
A11
PRES
Measured pressure
after zero adjustment
A15
OUTPUT mA
Output current
A16
ENGR. OUTPUT
User scaled value
A17
ENGR. EXP
Exponents
A20
SP %
Static pressure (in %)
A21
SP
Static pressure after
zero adjustment
A30
CAPSULE TEMP
Capsule temperature
A60
SELF CHECK
Self-diagnostics
B
SENSOR TYPE
Sensor type
B10
MODEL
Model and capsule type
B11
STYLE NO.
Style number
B20
PRES LRL
Lower range limit
B21
PRES URL
Upper range limit
B22
P MIN SPAN
Minimum span
B30
SP LRL
Lower range limit for
static pressure
B31
SP URL
Upper range limit for
static pressure
B32
SP MIN SPAN
Minimum span for static
pressure
B60
SELF CHECK
Self-diagnostics
C
BASIC SETUP
Setting data
C10 TAG NO.
Tag number
C20 PRES UNIT
Measurement range
unit
C21 PRES LRV
Lower range value
C22 PRES URV
Upper range value
C23 PRES POINT
Decimal place
C30 AMP DAMPING
Damping time constant
at amplifier
C40 OUTPUT MODE
Output mode
C60 SELF CHECK
Self-diagnostics
*1:
R/W: R = Read only, W = Read & Write
*2:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user's manual.
Item
R/W
*1
R
R
R
R
-2.5 to 110%
R
Unit specified in C20
R
3.6000 to 21.600 mA
R
Unit specified in I30
R
Unit specified in I32
R
-10 to 110%
R
Unit specified in D30
R
Unit specified in D40
R
Refer to Table 4.1 Alarm
Message Summary
R
Model and capsule type
R
Style number of product
R
Unit specified in C20
R
Unit specified in C20
R
Unit specified in C20
R
Unit specified in D30
R
Unit specified in D30
R
Unit specified in D30
R
See A60
W
16 alphanumeric characters As specified
W
mmH
2
mmHg, Torr, kPa, MPa,
mbar, bar, gf/cm
inH
O, inHg, ftH
2
atm, Pa, hPa
W
-32000 to 32000 within
measurement range
W
-32000 to 32000 within
measurement range
W
0 to 4
W
0.50 (0.00) to 100.00 sec,
see D50
W
LINEAR or SUQARE ROOT LINEAR or as
R
See A60
<8. Parameter Summary>
Content
Default value
EJX (for EJX series)
EJA (for EJA series)
As specified
GOOD
O, mmAq, mmWG,
kPa
2
, kgf/cm
2
,
O, psi,
2
As specified
As specified
2
2.00 sec or as
specified
specified
42
Applicable model
F
P
L
IM 01C25A01-01E