Guardian 4389 Diagnostic Repair Manual page 115

Automatic home standby generators
Hide thumbs Also See for 4389:
Table of Contents

Advertisement

SECTION 4.4
DIAGNOSTIC TESTS
meter to the output lugs of the generator main line
circuit breaker.
The fuel regulator is fitted with one (7 kW), or two (12 &
15 kW) adjustment screws. While watching the
frequency meter, slowly turn the adjustment screw(s)
clockwise or counterclockwise one at a time until
highest frequency is read on the meter.
Note: Only limited adjustment is available between
the set pins on 7 kW fuel regulators. Under no
circumstance should any of the pins be removed (see
Figures 30 & 31).
6. When the highest frequency is reached, maximum
power has been set. From this point turn the adjustment
screw(s) 1/4 turn counterclockwise. The regulator is
now set.
Figure 30
Figure 31
Page 4.4-18
PART 4
7. Turn utility power to the main distribution panel back on.
This can be done by switching the service main breaker
to the "ON" or closed position. Allow the generator to
shut down.
Do not make any unnecessary adjustments. Factory
settings are correct for most applications. However,
when making adjustments, be careful to avoid
overspeeding the engine.
TEST 64 - CHECK BATTERY CHARGE
OUTPUT
DISCUSSION:
The battery charging system is a two amp trickle
charge. It is capable of maintaining a charge on a
functional battery. It is not intended to, nor capable of
charging a completely dead battery.
The system will charge when utility source power is
available to the generator or if the generator is
running. The system consists of a transformer (TX),
battery charge relay (BCR), battery charger (BC), and
a battery charge winding. The BCR contacts allow AC
voltage to the battery charger. When the BCR is de-
energized, voltage from the TX is available to the
battery charger. When the generator starts, Wire 14
energizes the BCR. This allows battery charge
winding AC output to power the battery charger.
PROCEDURE:
1. Check the 5 amp fuse (F2).
2. Set the AUTO-OFF-MANUAL switch to OFF.
Note: Utility source voltage MUST be available to the
generator.
3. Set a VOM to measure DC amps.
4. Disconnect Wire 13A (purple) from the 5 amp fuse (F2).
5. Connect the positive (+) test lead to Wire 13A, and
connect the negative (-) test lead to the fuse (F2)
terminal from which Wire 13A was removed. The VOM
should measure 50 milliamps to 2.5 amps, depending
upon the state of the charge of the battery.
6. Repeat Step 5. This time set the AUTO-OFF-MANUAL
switch to MANUAL. Allow the generator to start and
then measure the current again as in Step 5.
RESULTS:
Follow the Flow Chart on Page 4.3-5.
DC CONTROL

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

47584456475943904760

Table of Contents