Gfci Operation - Honda EB5000i Owner's Manual

Honda generator
Hide thumbs Also See for EB5000i:
Table of Contents

Advertisement

OPERATION
GFCI OPERATION CHECK
Always check GFCI operation before using the generator.
1.
Unplug all tools and appliances from the generator.
2.
Start the engine (see page
3.
Turn the AC circuit breaker to the ON position.
4.
Press the GFCI TEST button. The RESET button should extend, and
the AC circuit breaker should switch to the OFF position.
If the GFCI and AC circuit breaker do not function as described, take
the generator to an authorized Honda generator dealer for repair.
32
A faulty GFCI can cause electric
shock which can seriously injury or
kill you.
Always perform the GFCI inspection
before using the generator. If the
GFCI fails the test, the generator
must be repaired by an authorized
Honda servicing dealer before use.
28
).
GFCI TEST BUTTON
GFCI RESET BUTTON