Table 5-2
Troubleshooting Reference
Problem
No output voltage. The status
LED is red.
No output voltage with shore
power connected.
No output voltage in inverter
mode.
The problem is not described
in this table.
975-0263-01-01
Possible Cause
Low input voltage (fault
code E02)
High input voltage (fault
code E03)
Thermal shutdown (fault
code E08)
Unit overload (fault code
E05)
Unit has a short-circuited
output (fault code E05).
Shore power has dropped
below 90 V.
GFCI has tripped.
15 A supplementary
circuit breaker has
tripped.
GFCI has tripped.
Troubleshooting Reference
Solution
Recharge the battery; check the
connections and cable.
Make sure the XM Series Inverter is
connected to a 12 V battery.
Check the voltage regulation of the
charging system.
Allow the unit to cool off. Reduce the load
if continuous operation is required.
Improve ventilation. Make sure the
inverter's ventilation openings are not
obstructed.
Reduce the ambient temperature.
Reduce the load. Make sure the load does
not exceed the XM Series Inverter's
output rating.
Remove the short circuit.
Check shore power voltage.
Turn inverter on.
Check load, and reset the GFCI.
Reset supplementary circuit breaker.
Check load, and reset the GFCI.
Visit www.xantrex.com/support.asp and
check the FAQs (Frequently Asked
Questions) for your product.