Installation
To make a permanent connection to existing AC wiring:
1. Install the required circuit breaker in the AC load panel.
2. Ensure AC power is turned off.
3. Remove the left-hand side AC wiring knockout from the front of the
4. Install a supplied strain-relief clamp in the AC knockout.
5. Locate the terminal block.
6. Strip about 2 inches (50 mm) from the jacket of the AC output cable.
7. Strip approximately 3/8 inch (10 mm) off the insulation of each
8. Run the AC cable through the left-hand side strain-relief clamp and into
9. Fasten the Ground wire to the grounding screw.
10. Using the 1/8 inch slot screwdriver, loosen the wire attachment screws
11. Insert the Line and Neutral wires into the corresponding terminals.
12. Tighten the wire attachment screws to a torque of 1.3–1.8 lbf-ft (1.76–
3–18
unit.
Important:
The applicable installation code may not allow you to run the AC
input and AC output wiring through the same AC knockout.
The two output terminals are labelled as follows:
N (neutral)
L (line)
A separate screw is provided to connect the AC output ground.
The AC output cable may be either solid or stranded, but must have
three conductors and sized as in Table 3-3 on page 3–14. (The AC
terminal block accepts wire sizes up to No. 10 AWG.)
conductor.
the wiring compartment.
on the terminals.
CAUTION: Reverse polarity
Improper connections (connecting a line conductor to a neutral conductor, for
example) will cause the XM Series Inverter to malfunction and may permanently
damage the inverter. Damage caused by a reverse polarity connection is not
covered by your warranty.
2.44 Nm). Leave some wiring slack inside the wiring compartment.
975-0263-01-01