B. Install Fireplace & Chimney
Install as per Sections 7 and 8.
C. Install Chase Top
You MUST use a chase top in a chase installation. Chase
tops are available from your Heat & Glo dealer or may
be field constructed.
Include a turndown and drip edge to prevent water from
seeping into the chase.
Include a 2 in. (51 mm) soldered, welded or spun collar
around pipe opening to keep water out.
Provide a 1/8 in. (3 mm) gap around the flue pipe.
Slope the chase top downward away from the opening.
WARNING! Risk of Fire! DO NOT caulk the pipe to the
chase top collar.
Caulk all seams to prevent leaks.
Refer to Figure 9.3.
Slope Downward
(1/4 in. per foot
minimum)
Figure 9.3 Chase Top Construction
D. Install Termination Cap
Install the chimney sections up through the chase enclo-
sure.
Caulk the overlap seam of any exposed pipe sections
that are located above the roof line to prevent leaks.
Refer to termination cap instructions.
WARNING! Risk of Fire! The minimum overlap of cap
to pipe (as shown in the following illustrations) MUST
be met or chimney may separate from cap. Separation
allows sparks, heat and embers to escape.
NOTICE: Paint the termination cap with a rust-resistant
paint to protect against the effects of corrosion on those
parts exposed to the weather.
Page 52
2 in. (51 mm) Collar
on Chase Top
Turn-down
Drip Edge
Chase
.018 (26 ga) min.
Galvanized
Chase Top
Heat & Glo • NorthStar EPA Fireplace • 480-1081E
TR344 Round Termination Cap
Slip
storm collar
around chimney pipe
before termination
cap pipe is snapped
into the chimney
pipe.
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Termination cap pipe and chimney section must be snapped
together to maintain an overlap of 1-1/2 in. (38 mm).
Figure 9.4
Installing a TR344 Round Termination Cap
TR342 Round Telescoping Termination Cap
Assemble
Termination
storm collar
around extended
termination cap
pipe
once cap is
installed.
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)
Figure 9.5
Installing a TR342 Round Telescoping Termination Cap
Termination
Cap
Do NOT
block air holes
6 in. (153 mm)
Storm
Minimum top of
Collar
chase to top of
chimney pipe
Chimney
Pipe
Chase
Cap
Do NOT
block air
holes
Storm
Collar
3 clip brackets.
Slip over chase collar
and attach with screws
provided.
14 1/2 in. (368 mm)
Maximum
Chase
Chimney
Pipe
4/20/11