Input Voltage Is Out Of Range; Insufficient Warning Of Low Batteries; Internal Ups Fault Condition; Low Battery Shutdowns - HP R5000 User Manual

4500 w
Hide thumbs Also See for R5000:
Table of Contents

Advertisement

Power down the UPS
a.
Remove one or more load devices to reduce the power requirements.
b.
Wait at least 5 seconds and restart the UPS.
c.
If the condition persists, verify that the load devices are not defective.
d.
Allow the UPS to cool:
4.
Power down the UPS
a.
Clear vents and remove any heat sources.
b.
Verify that the airflow around the UPS is not restricted.
c.
Wait at least 5 minutes and restart the UPS.
5.
If the condition persists, contact an HP authorized service representative.
6.

Input voltage is out of range

Action:
Check the input voltage and reconfigure the UPS
1.
Contact a qualified electrician to verify that the utility power is suitable for the UPS.
2.

Insufficient warning of low batteries

Action:
Verify that the power management software is not delaying the shutdown of attached servers when the
1.
UPS is in a low battery condition.
Allow the UPS batteries to charge for 48 hours.
2.
If a Battery Fault occurs, replace the batteries.
3.

Internal UPS fault condition

Action:
Power down the UPS
1.
If the condition persists, contact an HP authorized service representative.
2.

Low battery shutdowns

Possible cause::Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.
Action:
Verify that the power management software is not delaying the shutdown of attached servers when the
1.
UPS is in a low battery condition.
Allow the UPS batteries to charge for 48 hours.
2.
If a Battery Fault occurs, replace the batteries.
3.
("Powering down the
("Powering down the
("Powering down the
UPS" on page 34).
UPS" on page 34).
UPS" on page 34).
("Configuring the
UPS" on page 32).
Troubleshooting 47