Generator Start-Up Procedure - MULTIQUIP Power Ultra-Silent DCA-45USI Operation And Parts Manual

Ultra-silent series generator
Table of Contents

Advertisement

WARNING:
WARNING:
WARNING:
WARNING:
WARNING:
The engine's exhaust contains harmful
emissions. ALWAYS have adequate
ventilation when operating . Direct exhaust
away from nearby personnel.
Before Starting
CAUTION:
NEVER! manually start the engine with the
main, GFCI or auxiliary circuit breakers in
the ON (closed) position.
1. Be sure and place the main, G.F.C.I. and aux. circuit
breakers (Figure 40) in the OFF position prior to starting
the engine.
Figure 38. Main, Aux. and GFCI
2. Connect the load to the Output Terminal Lugs or
auxiliary receptacles as shown in Figure 39. These load
connection points can be found on the output terminal
panel.
Figure 39. Load Connections
PAGE 36 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)
DCA-45USI — GENERATOR START-UP PROCEDURE
Circuit Breakers
3. Close all engine enclosure doors (Figure 40).
Figure 40. Engine Enclosure Doors
4. Place the voltage selector switch in the desired voltage
position (Figure 41).
Figure 41. Voltage Selector Switch
5. Preheat the engine glow plugs by turning the ignition
key (Figure 42) to the PRE-HEAT/RUN position. When
the preheat lamp (Figure 43) turns off, proceed
to step 6.
Figure 42. Ignition Switch
(Pre-Heat/Run Position)
Figure 43. Pre-Heat Indicator Lamp