Table 4-1 Lower Display Key Parameter Prompts - Honeywell UDC3300 User Manual

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

Setpoint Rate/Ramp/Soak Program Operation

Table 4-1 Lower Display Key Parameter Prompts

Indication
OUT
OUTPUT #1—Output value is percent; for Three Position Step control, this is
an estimated motor position when no slidewire exists.
OT2
OUTPUT #2—Appears only if 2-loop or Cascade control is configured.
LOCAL SETPOINT #1—Also current setpoint when using SP Ramp.
SP
2SP
LOCAL SETPOINT #2
LOCAL SETPOINT #3
3SP
RSP
REMOTE SETPOINT
INPUT 1—Used only with combinational input algorithms.
1IN
2IN
INPUT 2
INPUT 3
3IN
POS
SLIDEWIRE POSITION—Used only with TPSC.
COMPUTER SETPOINT—When SP is in override.
CSP
DEVIATION—Maximum negative display is –999.9.
DEV
PIDSETX
TUNING PARAMETER SET 1—Selected set for single loop or primary loop
configuration where X is either 1 or 2.
2PIDSETX
TUNING PARAMETER SET 2—Selected set for secondary loop configuration
where X is either 1 or 2.
ET XX.XX
ELAPSED TIME—Time that has elapsed on timer in Hours.Minutes.
TIME REMAINING—Time that remains on timer in Hours.Minutes
TR XX.XX
RAMPXXXM
SETPOINT RAMP TIME—Time remaining in the setpoint ramp in minutes.
Soak # and TIME REMAINING IN SOAK
O SK XXXX
1PV
PROCESS VARIABLE 1—For Cascade or 2-loop applications.
PROCESS VARIABLE 2—For Cascade or 2-loop applications.
2PV
AUX
AUXILIARY OUTPUT—Displayed only when Loop 2 is not used, or when Loop
2 is Time Simplex and Loop 1 is not Current Duplex.
OC1
CHARACTERIZED OUTPUT 1—Displayed if Loop 1 output is characterized.
CHARACTERIZED OUTPUT 2—Displayed if Loop 2 output is characterized.
OC2
SPn
SP RATE SETPOINT—Current setpoint for setpoint rate applications
6LJPD
CURRENT TOTALIZATION VALUE—Displays the total flow volume being
measured.
BIAS—Displays the manual reset value for algorithm PD+MR.
BIA
TUNE OFF
LIMIT CYCLE TUNING NOT RUNNING—Appears when Accutune is disabled.
LIMIT CYCLE TUNING RUNNING—Appears when Accutune is enabled.
TUNE RUN
ToBEGIN
RESET SP PROGRAM TO BEGINNING OF FIRST SEGMENT
OUTPUT OVERRIDE (2 PID LOOPS ONLY)—Appears when internal Loop 1
OTI
Output value is displayed. This represents the internal output 1 value before
override.
54