If the load current is less than the minimum rated value of 20 mA, there may be a residual voltage
across both ends of the load even if the relay is turned off. Use a dummy resistor as shown to
counteract this. The total current through the resistor and the load current must exceed 20 mA.
2
Alarm #2 not available with Time Proportional Duplex or Three Position Step Control or Position
Proportional control.
Solid State relays are rated at 0.5 amps. Customer should size fuses accordingly. Use Fast Blo
3
fuses only.
Electromechanical relays are rated at 5 Amps @120 Vac or 30 Vdc and 2.5 Amps at 240 Vac.
4
Customer should size fuses accordingly. Use Fast Blo fuses only.
WARNING: Only connect Vac to solid
Figure 2-8 Solid State (SS) Relay Output — Model DC33-X-AA-XX
10
1
+
11
2
12
3
13
4
14
+
5
15
6
16
7
17
8
9
Figure 2-9 10-amp SS External Relay Output — Model DC330X-SS-XX
5/00
Time Proportional
Relay Load
Dummy Resistor
2
Relay Load
Dummy Resistor 1
Alarm Relay #1 Load
To terminal
7 or 9
L2/N
LOAD
L1
HOT
Black
Output 1
White
Output 2
Green
UDC3300 Expanded Model: DC330E User Manual
3
1
3
4
state relays.
1
AC
+
Solid State
Relay
Installation
AC Load
Supply
Power
AC Load
Supply
Power
AC Load
Supply
Power
External solid
1
state relays are
rated at 15 amps
@25°C derated
to 10 amps at
55°C. Customer
should size fuses
accordingly. Use
Fast Blo fuses
only.
11