Honeywell UDC3300 User Manual page 51

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

Function
Prompt
Lower Display
Output Change Rate
OUT RATE
PCT/M UP
Output Rate Up Value
PCT/M DN
Output Rate Down Value
High Output Limit
OUTHiLIM
Low Output Limit
OUTLoLIM
High Reset Limit
I Hi LIM
Low Reset Limit
I Lo LIM
DROPOFF
Controller Dropoff Value
Output Relay Deadband
DEADBAND
Output Relay Hysteresis
OUT HYST
Failsafe Mode
FAILMODE
FAILSAFE
Failsafe Output Value for
all outputs except 3P Step
Failsafe Output Value for
3P Step
PDMR/Position Propor-
SW FAIL
tional motor position when
slidewire fails.
MAN OUT
Power-up Preset Output
for Manual Output
Power-up Preset Output
AUTO OUT
for Automatic Output
Proportional Band or Gain
PBorGAIN
Units
Reset Units
MINorRPM
5/00
Function
Name
UDC3300 Expanded Model: DC330E User Manual
Selections or
Range of Setting
Upper Display
ENABLE
DISABL
Does not apply to 3 Position Step
Control algorithm.
0 to 9999 % per minute
0 to 9999 % per minute
–5.0 to 105 % of output
–5.0 to 105 % of output
Within the range of the output
limits
Within the range of the output
limits
–5 to 105 % of output
Time Duplex:
–5.0 to 25.0 %
On/Off Duplex:
0.0 to 25.0 %
Position Prop. and 3P Step:
0.5 to 5.0 %
0.0 to 100.0 % of PV Span for
On/Off control.
NO LAT
LATCH
Set within the range of the output
limits. 0 to 100 %
0 PCT (motor to closed position)
100PCT (motor to open position)
0 PCT (motor to closed position)
100PCT (motor to open position)
Within the range of output limits
Within the range of output limits
PB PCT
GAIN
RPM
MIN
Configuration
Factory
Setting
DISABL
0
0
100
0.0
100.0
0.0
0
1.0
0.5
NO LAT
0.0
- -
- -
- -
GAIN
MIN
41