Honeywell HE220 Installation Manual & Owner's Manual page 5

By-pass flow-through humidifier

Advertisement

Available languages

Available languages

Required Tools
Tools required for installation include:
• Tin snips.
• Screwdriver.
• Adjustable or open-end wrench.
• Level.
• Work Gloves (preferably cut resistant)
• Safety Glasses
• Battery-powered Drill, punch or awl.
CAUTION
Voltage Hazard.
Use a battery-powered drill to avoid electrocution if inadvertently coming into
contact with water in plumbing lines.
INSTALLATION
Preparing for the Installation
Be sure to identify all the required (Table 1) accessories (included) and make sure the
appropriate tools are available before beginning the installation.
Determining Best Location for Humidifier
CAUTION
Temperature and Static Pressure Hazard.
Can cause property or equipment damage.
Locate humidifier where ambient temperature is between 32°F (0°C) and
160°F (71°C).
Do not install humidifier where freezing temperatures could occur.
Be sure supply plenum static pressure is no greater than 0.4 in. wc and water
pressure is no greater than 124 psi.
• Select a location for the humidifier on the supply (warm air stream) plenum.
See Fig. 1.
• Select a location that cannot damage the air conditioner A-coil during installation.
• Do not locate the humidifier on the furnace body.
• Allow adequate clearance in front of and above the humidifier so you can easily
remove the cover to perform routine maintenance.
— Mount the humidifier at least 3 in. (78 mm) above the furnace body to allow
adequate space for the solenoid valve and drain line.
— Mount the humidifier in a conditioned space to prevent freezing.
HE220 AND HE260 BY-PASS FLOW-THROUGH HUMIDIFIER
5
69-1111EF—05