Weber Vieluxe 27 Built-In Grill Installation Manual page 5

Built-in liquid propane gas grill
Hide thumbs Also See for Vieluxe 27 Built-In Grill:
Table of Contents

Advertisement

floor level. The ventilation openings should have a
total free area of not less than 10 square inches.
(This relates to 1/2 square of ventilation area, per
pound of stored fuel capacity). There should be at
least two ventilation openings if the ventilation
openings at floor level are in the sidewall. The
ventilation openings should be within 5 inches
(127mm) of the floor. The ventilation openings
should be of equal size and be spaced at a
minimum of 90 degrees, and should be
unobstructed.
3. The minimum size of the ventilation hole (s) should
not be less than 1/4 inch.
4. The ventilation openings in the sidewalls should not
allow venting into the empty or "hollow" area of the
"island". If a gas leak should occur or the LP
cylinder should vent in the LP cylinder enclosure,
the gas should not be allowed to vent or migrate
into the empty or "hollow" area of the "island".
Ventilation openings in the sidewalls of the
enclosure should only communicate with the
outside of the "island" structure, so that the gas can
dissipate outside of the "island" structure.
c. If the remote LP cylinder enclosure has four sides, a
top and a bottom, and is intended for installation in a
built-in "island" enclosure;
1. At least one ventilation opening (a hole or group of
holes, for the purpose of ventilation) needs to be on
one side of the enclosure that communicates with
the outside of the "island" structure. If a gas leak
should occur or the LP cylinder should vent in the
LP cylinder enclosure, the gas should not be
allowed to vent or migrate into the empty or
"hollow" area of the "island". Ventilation openings
should only communicate with the outside of the
"island" structure, so that the gas can dissipate
outside of the "island" structure. The ventilation
opening should be located within 5 inches (127mm)
of the top of the enclosure, and should have a total
free area of 20 square inches. (This relates to 1
square inch of ventilation area, per pound of stored
fuel).
2. At least one ventilation opening (a hole or group of
holes, for the purpose of ventilation) needs to be on
one side of the enclosure that communicates with
the outside of the "island" structure, at the bottom. If
a gas leak should occur or the LP cylinder should
vent in the LP cylinder enclosure, the gas should
not be allowed to vent or migrate into the empty or
"hollow" area of the "island". Ventilation openings
should only communicate with the outside of the
"island" structure, so that the gas can dissipate
outside of the "island" structure. The ventilation
opening should be located within 5 inches (127mm)
of the bottom of the enclosure, and should have a
total free area of 10 square inches. (This relates to
1/4 square inch of ventilation area, per pound of
stored fuel).
3. The minimum size of the ventilation hole (s) should
not be less than 1/4 inch.
d. The remote LP cylinder enclosure should be
constructed with non-combustible materials. The
remote LP cylinder enclosure should isolate the LP
cylinder from the burner compartment, so that it
provides shielding from radiation, be a flame barrier
and provide protection from foreign material such as
hot drippings.
e. There should be a minimum of 2 inches (50.8mm)
between the ground and the floor of the remote LP
cylinder enclosure.
f. The LP cylinder valve should be readily accessible for
hand operation. A door on the remote LP cylinder
enclosure to gain access to the LP cylinder valve is
acceptable, provided it is non- locking and can be
opened without the use of tools.
If your, licensed contractor or licensed plumber, builds an
LP cylinder enclosure following the guidelines in the ANSI
Standard for Outdoor Cooking Gas Appliances,
Z21.58/CSA1.6, you need to order kit number (36300),
which will contain the hose and regulator assembly and
connecting fittings that must be used with the Vieluxe
gas grill. The hose and regulator in the kit (36300) is listed
as part of the CSA listed Vieluxe
contains the parts necessary for cylinder retention.
Use of any other hose and regulator assembly could
be dangerous, and may not provide adequate gas
supply to the Vieluxe
fire or an explosion causing serious bodily injury or
death and damage to property.
Failure to use the the Vieluxe
cylinder or failure to build a LP cylinder enclosure for
a 20 lb cylinder following the requirements for
ventilation, cylinder retention and separation of the
LP cylinder from a heat source, listed in the ANSI
Standard for Outdoor Cooking Gas Appliances, ANSI
Z21.58/CSA1.6, could be dangerous, and could result
in a fire or an explosion causing serious bodily injury
or death and damage to property.
If you do not follow the DANGER statements exactly,
the Warranty on the Vieluxe
5
®
gas grill. The kit also
DANGER:
®
gas grill, and could result in a
DANGER:
®
Tank Cabinet for a 20 lb
®
gas grill will be voided.
®