Weber Vieluxe 27 Built-In Grill Installation Manual page 3

Built-in liquid propane gas grill
Hide thumbs Also See for Vieluxe 27 Built-In Grill:
Table of Contents

Advertisement

TYPICAL BULK PROPANE
GAS SUPPLY
INSTALLATION
WE RECOMMEND THAT THIS INSTALLATION BE
DONE BY A LICENSED PROFESSIONAL.
General Specifications for Piping
Note - Contact your local municipality for building
codes regulating outdoor gas grill installations. In
absence of Local Codes, you must conform to the
latest edition of ANSI Z223.1/NFPA 54.
■ This grill is designed to operate at 10.5 inches of
water column pressure. A LP in line regulator may be
necessary to acheive this pressure.
CAUTION: If young children are in the area, a
locking valve should be considered.
■ Pipe compound should be used which is resistant to the
action of liquid propane gas when gas connections
are made.
■ The gas connections must be firmly attached to rigid,
permanent construction.
Note: The information provided in this manual is
general for typical installations. We cannot cover all
possible installation ideas. We recommend, prior to
installation, that you contact your municipality for
local building codes and your local fire department
for installation requirements.
If you have any questions, contact the Vieluxe
Table 10-1
Nominal
Iron Pipe Interal
Size
Diameter
(inches) (inches)
1/4
3/8
1/2
3/4
1
1.049
1 1/4
1.380
1 1/2
1.160
2
2.067
2 1/2
2.469
3
3.068
4
4.026
©1997 National Fire Protection Association, Inc., and International Approval Services - U.S., Inc. All Rights Reserved.
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and
a Pressure Drop of 0.3 Inch Water Column.
(Based on a 0.60 Specific Gravity Gas)
10
20
30
40
.364
32
22
18
15
.493
72
49
40
34
.622
132
92
73
63
.824
278
190
152
130
520
350
285
245
1050
730
590
500
1600 1100
890
760
3050 2100 1650 1450 1270 1150 1050
4800 3300 2700 2300 2000 1850 1700 1600 1500 1400 1250 1130
8500 5900 4700 4100 3600 3250 3000 2800 2600 2500 2200 2000
17500 12000 9700 8300 7400 6800 6200 5800 5400 5100 4500 4100
Gas line piping
■ Refer to the piping chart at the bottom of the page.
■ The corrugated gas line from the manifold is
48 inches long. Do not extend the gas line.
■ We have provided the means to make an SAE 45°
flare connection. Do not use pipe sealant on
this connection.
■ If the length of line required does not exceed 50 feet,
use a 5/8" O.D. tube. One size larger should be used
for lengths greater than 50 feet.
Refer to piping chart below.
■ Gas piping may be copper tubing, type K or L;
polyethylene plastic tube, with a minimum wall
thickness of .062 inch; or standard weight (schedule
40) steel or wrought iron pipe.
■ Check you local building codes.
®
Customer Service Center at 1-866-VIELUXE.
Piping Chart
Length of Pipe (Feet)
50
60
70
80
90
14
12
11
11
10
30
27
25
23
22
56
50
46
43
40
115
105
96
90
84
215
195
180
170
160
440
400
370
350
320
670
610
560
530
490
990
930
3
100
125
150
175
200
9
8
8
7
6
21
18
17
15
14
38
34
31
28
26
79
72
64
59
55
150
130
120
110
100
305
275
250
225
210
460
410
380
350
320
870
780
710
650
610
1050 980
1850 1700
3800 3500

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vieluxe 39 built-in grillVieluxe 360251Vieluxe 370251

Table of Contents