To configure the SNMP settings:
Select the SNMP version supported by the UPS Network Module from the Version pull-down menu.
1.
Available options are Disabled, V1, V3, and V1 and V3.
Configure the SNMP V1 settings:
2.
Enter the SNMP Community Read-Only string. The UPS Network Module and the Clients must share
a.
the same community name to communicate.
Select or clear the SNMP Write Enabled checkbox to enable or disable the SNMP write function.
b.
If the SNMP write function is enabled, enter the SNMP Community Write string. The UPS Network
c.
Module and the Clients must share the same community name to communicate.
Configure the SNMP V3 settings:
3.
Enter a user name for the Read-Only User. This user is only authorized to read SNMP variables.
a.
Select a level of security from the Read-Only Security Level pull-down menu:
b.
No Auth No Priv—The user does not use authentication and privacy to access SNMP variables.
Auth No Priv—The user must use authentication, but not privacy, to access SNMP variables.
Auth Priv—The user must use authentication and privacy to access SNMP variables.
Enter the Read-Only Password to specify a new password for the Read-Only User. The password
c.
can be between 8 and 24 alphanumeric characters and the <>&@#%_=:;,./?|$*() symbols.
Enter a user name for the Read-Write User. This user is authorized to read and write SNMP
d.
variables.
Select a level of security from the Read-Write Security Level pull-down menu:
e.
No Auth No Priv—The user does not use authentication and privacy to access SNMP variables.
Auth No Priv—The user must use authentication, but not privacy, to access SNMP variables.
Auth Priv—The user must use authentication and privacy to access SNMP variables.
Enter the Read-Write Password to specify a new password for the Read-Write User. The password
f.
can be between 8 and 24 alphanumeric characters and the <>&@#%_=:;,./?|$*() symbols.
Enter a user name to include in SNMPV3 notification in the Notification Username field. This field
g.
must also be defined in the applications that receive the notifications. The user name can be
between 8 and 24 alphanumeric characters and the <>&@#%_=:;,./?|$*() symbols.
Click Save.
4.
Click Help to view online help.
HP UPS Network Module web interface 41