High-Voltage Ups Battery Runtimes; Low-Voltage Ups Battery Runtimes; Environmental Specifications; Repo Port Specifications - HP R1500 - UPS XR User Manual

Hp r/t3000 g2 ups user guide
Table of Contents

Advertisement

Feature
Charging

High-voltage UPS battery runtimes

Load, percent
20
50
80
100

Low-voltage UPS battery runtimes

Load, percent
20
50
80
100

Environmental specifications

Feature
Operating temperature
Nonoperating
temperature
Relative humidity
Operating altitude
Nonoperating altitude
Audible noise

REPO port specifications

The REPO port meets the requirements of NFPA 70 and NEC Articles 645-10 and 645-11 for a
Disconnecting Means.
Specification
Complete charge takes no more than 48 hours. After
approximately 3 hours, the batteries reach 80% charge at default
nominal utility voltage and no load.
Estimated battery
runtime
40 minutes
12 minutes
6 minutes
4 minutes
Estimated battery
runtime
45 minutes
15.5 minutes
7 minutes
5 minutes
Specification
10°C to 40°C (50°F to 104°F); UL-tested at 25°C
(77°F)
-15°C to 40°C (-5°F to 104°F)
20% to 80%; noncondensing
Up to 3,000 m (9,842 ft) above sea level
15,000 m (49,212 ft) above sea level
Less than 45 dBA, normal operation
Less than 50 dBA, on battery power
Runtime with one ERM
125 minutes
50 minutes
30 minutes
24 minutes
Runtime with one ERM
142 minutes
55 minutes
34 minutes
26 minutes
Runtime with two ERMs
225 minutes
89 minutes
54 minutes
43 minutes
Runtime with two ERMs
256 minutes
99 minutes
60 minutes
47 minutes
Specifications 63